@prefix rdf: . @prefix rdfs: . @prefix xsd: . @prefix owl: . @prefix ph: . @prefix phScience: . @prefix phIoT: . ph:hasTag a owl:ObjectProperty ; rdfs:range ph:marker . _:b-0000 a phIoT:site ; ph:hasTag phIoT:site ; rdfs:label "Bravo" ; phIoT:area 78000 ; ph:dis "Bravo" ; ph:geoAddr "123 Some Rd, Fort Wayne, IN 46900" ; ph:geoCity "Fort Wayne" ; ph:geoCountry "US" ; ph:geoCounty "US" ; ph:geoPostalCode "46900" ; ph:geoState "IN" ; ph:geoStreet "123 Some Rd" ; phIoT:primaryFunction "Hospital (General Medical & Surgical)" ; ph:tz "Chicago" ; phIoT:weatherStationRef _:b-042f ; phIoT:yearBuilt 2000 ; _:custom _:0b111ff8-37ee-4100-38cf-f23c91a70cca . _:0b111ff8-37ee-4100-38cf-f23c91a70cca rdfs:label "" ; _:elecFreq 60 . _:b-0001 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-1" ; ph:dis "Bravo BCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0b111ff8-37ee-4101-38d0-f23c91a70cca . _:0b111ff8-37ee-4101-38d0-f23c91a70cca rdfs:label "" . _:b-0002 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-1 Cooling Valve Output" ; ph:dis "Bravo BCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-37ee-4102-38d1-f23c91a70cca . _:0b111ff8-37ee-4102-38d1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.31259757180034364 ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0003 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-1 Mixed Air Damper Output" ; ph:dis "Bravo BCU-1 Mixed Air Damper Output" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-37ee-4103-38d2-f23c91a70cca . _:0b111ff8-37ee-4103-38d2-f23c91a70cca rdfs:label "" ; _:predictionConf 0.28394372966813813 ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0004 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-1 Supply Air Temperature" ; ph:dis "Bravo BCU-1 Supply Air Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37ee-4104-38d3-f23c91a70cca . _:0b111ff8-37ee-4104-38d3-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7893816782198223 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0005 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature" ; ph:dis "Bravo BCU-1 Zone Temperature" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37fd-8340-38d4-f23c91a70cca . _:0b111ff8-37fd-8340-38d4-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6720981954640639 ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0006 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0001 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37fd-8341-38d5-f23c91a70cca . _:0b111ff8-37fd-8341-38d5-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0007 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:chilledWaterCooling, phIoT:equip, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo BCU-2" ; ph:dis "Bravo BCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; _:custom _:0b111ff8-37fd-8342-38d6-f23c91a70cca . _:0b111ff8-37fd-8342-38d6-f23c91a70cca rdfs:label "" . _:b-0008 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo BCU-2 Cooling Valve Output" ; ph:dis "Bravo BCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-37fd-8343-38d7-f23c91a70cca . _:0b111ff8-37fd-8343-38d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlvOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0009 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:mixed, phIoT:point ; rdfs:label "Bravo BCU-2 Mixed Air Damper Output" ; ph:dis "Bravo BCU-2 Mixed Air Damper Output" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-37fd-8344-38d8-f23c91a70cca . _:0b111ff8-37fd-8344-38d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "MadOR_value" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-000a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo BCU-2 Supply Air Temperature" ; ph:dis "Bravo BCU-2 Supply Air Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37fd-8345-38d9-f23c91a70cca . _:0b111ff8-37fd-8345-38d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature" ; ph:dis "Bravo BCU-2 Zone Temperature" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37fd-8346-38da-f23c91a70cca . _:0b111ff8-37fd-8346-38da-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-000c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo BCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo BCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0007 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-000d ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-37fd-8347-38db-f23c91a70cca . _:0b111ff8-37fd-8347-38db-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-000d a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo BCUs" ; ph:dis "Bravo BCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-37fd-8348-38dc-f23c91a70cca . _:0b111ff8-37fd-8348-38dc-f23c91a70cca rdfs:label "" . _:b-000e a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 1" ; ph:dis "Bravo Boiler 1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0b111ff8-37fd-8349-38dd-f23c91a70cca . _:0b111ff8-37fd-8349-38dd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-000f a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 1 Boiler Status" ; ph:dis "Bravo Boiler 1 Boiler Status" ; phIoT:equipRef _:b-000e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-382b-4a00-38de-f23c91a70cca . _:0b111ff8-382b-4a00-38de-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr1Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0010 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Boiler 2" ; ph:dis "Bravo Boiler 2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; _:custom _:0b111ff8-382b-4a01-38df-f23c91a70cca . _:0b111ff8-382b-4a01-38df-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterPower 4200 ; _:designMake "Bryan Boiler" ; _:designModel "RV-500W" . _:b-0011 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Boiler 2 Boiler Status" ; ph:dis "Bravo Boiler 2 Boiler Status" ; phIoT:equipRef _:b-0010 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-383a-8c40-38e0-f23c91a70cca . _:0b111ff8-383a-8c40-38e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwBlr2Sts" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0012 a phIoT:hot-water-plant ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Boiler Plant" ; ph:dis "Bravo Boiler Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-0013 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:domestic, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; ph:dis "Bravo Boiler Plant Domestic Hot Water Leaving Temperature Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-383a-8c41-38e1-f23c91a70cca . _:0b111ff8-383a-8c41-38e1-f23c91a70cca rdfs:label "" ; _:sourcePointName "HwSp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0014 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:delta, phIoT:his, phIoT:hot, phIoT:point, phScience:pressure, phIoT:sp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; ph:dis "Bravo Boiler Plant Heating Hot Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0b111ff8-383a-8c42-38e2-f23c91a70cca . _:0b111ff8-383a-8c42-38e2-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0015 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heating, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Return Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Return Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-383a-8c43-38e3-f23c91a70cca . _:0b111ff8-383a-8c43-38e3-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0016 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; ph:dis "Bravo Boiler Plant Heating Hot Water Supply Temperature" ; phIoT:equipRef _:b-0012 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-383a-8c44-38e4-f23c91a70cca . _:0b111ff8-383a-8c44-38e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "HWSTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0017 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo CHW System" ; ph:dis "Bravo CHW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-383a-8c45-38e5-f23c91a70cca . _:0b111ff8-383a-8c45-38e5-f23c91a70cca rdfs:label "" . _:b-0018 a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-1" ; ph:dis "Bravo CHWP-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-0019 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-1 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-0018 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-383a-8c46-38e6-f23c91a70cca . _:0b111ff8-383a-8c46-38e6-f23c91a70cca rdfs:label "" ; _:poinTags "point and chilled and water and cmd and pump" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-001a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-1 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-0018 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-383a-8c47-38e7-f23c91a70cca . _:0b111ff8-383a-8c47-38e7-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-14T01:00:03.512-04:00"^^xsd:dateTime ; _:precision 2 ; _:dataSyncType "error" . _:b-001b a phIoT:equip ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo CHWP-2" ; ph:dis "Bravo CHWP-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:dis "Bravo CHWP-2 Chilled Water Pump Enable" ; ph:enum "Stop,Running" ; phIoT:equipRef _:b-001b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-383a-8c48-38e8-f23c91a70cca . _:0b111ff8-383a-8c48-38e8-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-001d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; ph:dis "Bravo CHWP-2 Chilled Water Pump VFD Speed" ; phIoT:equipRef _:b-001b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-383a-8c49-38e9-f23c91a70cca . _:0b111ff8-383a-8c49-38e9-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-001e a phIoT:chilled-water-plant ; ph:hasTag phIoT:chilled, phIoT:equip, phIoT:hvac, phIoT:plant, phScience:water ; rdfs:label "Bravo Chilled Water Plant" ; ph:dis "Bravo Chilled Water Plant" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 . _:b-001f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cooling, phIoT:cur, phIoT:enable, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Cooling Enable" ; ph:dis "Bravo Chilled Water Plant AHU Cooling Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-383a-8c4a-38ea-f23c91a70cca . _:0b111ff8-383a-8c4a-38ea-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUClgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0020 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:heating, phIoT:his, phIoT:point ; rdfs:label "Bravo Chilled Water Plant AHU Heating Enable" ; ph:dis "Bravo Chilled Water Plant AHU Heating Enable" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-383a-8c4b-38eb-f23c91a70cca . _:0b111ff8-383a-8c4b-38eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "AHUHtgEnable" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0021 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; ph:dis "Bravo Chilled Water Plant CV-1 Valve Signal (HHW)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-383a-8c4c-38ec-f23c91a70cca . _:0b111ff8-383a-8c4c-38ec-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0022 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:bypass, phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; ph:dis "Bravo Chilled Water Plant CV-2 Valve Signal (Bypass Valve)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-383a-8c4d-38ed-f23c91a70cca . _:0b111ff8-383a-8c4d-38ed-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0023 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-3 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-3 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-383a-8c4e-38ee-f23c91a70cca . _:0b111ff8-383a-8c4e-38ee-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0024 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo Chilled Water Plant CV-4 Valve Signal" ; ph:dis "Bravo Chilled Water Plant CV-4 Valve Signal" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; ph:maxVal 100 ; ph:minVal 0 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3849-ce80-38ef-f23c91a70cca . _:0b111ff8-3849-ce80-38ef-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0025 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0b111ff8-3849-ce81-38f0-f23c91a70cca . _:0b111ff8-3849-ce81-38f0-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0026 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:delta, phIoT:his, phIoT:primaryLoop, phIoT:point, phScience:pressure, phIoT:sensor, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; ph:dis "Bravo Chilled Water Plant Chilled Water Differential Pressure Setpoint" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "psi" ; _:custom _:0b111ff8-3849-ce82-38f1-f23c91a70cca . _:0b111ff8-3849-ce82-38f1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3397244142906628 ; _:sourcePointName "ChwDifSP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0027 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Entering Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3849-ce83-38f2-f23c91a70cca . _:0b111ff8-3849-ce83-38f2-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "CHWRTEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0028 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:primaryLoop, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; ph:dis "Bravo Chilled Water Plant Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3849-ce84-38f3-f23c91a70cca . _:0b111ff8-3849-ce84-38f3-f23c91a70cca rdfs:label "" ; _:predictionConf 0.787900067809321 ; _:sourcePointName "ChwsTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0029 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3849-ce85-38f4-f23c91a70cca . _:0b111ff8-3849-ce85-38f4-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-002a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chilled Water Plant Chiller Status" ; ph:dis "Bravo Chilled Water Plant Chiller Status" ; phIoT:equipRef _:b-001e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3849-ce86-38f5-f23c91a70cca . _:0b111ff8-3849-ce86-38f5-f23c91a70cca rdfs:label "" ; _:predictionConf 0.15013386549340826 ; _:sourcePointName "RunSTATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-002b a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; ph:dis "Bravo Chilled Water Plant Efficiency (Auto-computed)" ; phIoT:equipRef _:b-001e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "kW/ton" ; _:custom _:0b111ff8-3849-ce87-38f6-f23c91a70cca . _:0b111ff8-3849-ce87-38f6-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-002c a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0b111ff8-3849-ce88-38f7-f23c91a70cca . _:0b111ff8-3849-ce88-38f7-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-002d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3849-ce89-38f8-f23c91a70cca . _:0b111ff8-3849-ce89-38f8-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH1_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-002e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 1 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3849-ce8a-38f9-f23c91a70cca . _:0b111ff8-3849-ce8a-38f9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH1_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-002f a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 1 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3849-ce8b-38fa-f23c91a70cca . _:0b111ff8-3849-ce8b-38fa-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0030 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 1 Chiller 1 Setpoint" ; ph:dis "Bravo Chiller 1 Chiller 1 Setpoint" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3849-ce8c-38fb-f23c91a70cca . _:0b111ff8-3849-ce8c-38fb-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH1_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0031 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 1 Chiller Act. Capacity" ; phIoT:equipRef _:b-002c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3849-ce8d-38fc-f23c91a70cca . _:0b111ff8-3849-ce8d-38fc-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0032 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 1 Chiller Enable" ; ph:dis "Bravo Chiller 1 Chiller Enable" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10c0-38fd-f23c91a70cca . _:0b111ff8-3859-10c0-38fd-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH1_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0033 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 1 Chiller Status" ; ph:dis "Bravo Chiller 1 Chiller Status" ; phIoT:equipRef _:b-002c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10c1-38fe-f23c91a70cca . _:0b111ff8-3859-10c1-38fe-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH1_ChlrSts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0034 a phIoT:chiller ; ph:hasTag phIoT:airCooling, phIoT:chiller, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Chiller 2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo Chiller 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; _:custom _:0b111ff8-3859-10c2-38ff-f23c91a70cca . _:0b111ff8-3859-10c2-38ff-f23c91a70cca rdfs:label "" ; _:designElecPower 180 ; _:designEfficiency 10.6 ; _:designSource "Drawings" ; _:designChilledWaterPower 160 ; _:designChilledWaterLeavingTemp 44 ; _:designMake "Mcquay" ; _:designChilledWaterEnteringTemp 58 ; _:designChilledWaterDeltaPressure 18.61 ; _:designModel "AGS-160C" ; _:designChilledWaterFlow 275 . _:b-0035 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:entering, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Entering Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Entering Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3859-10c3-3900-f23c91a70cca . _:0b111ff8-3859-10c3-3900-f23c91a70cca rdfs:label "" ; _:predictionConf 0.38428817764444545 ; _:sourcePointName "CH2_EntChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0036 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sensor, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chilled Water Leaving Temperature" ; ph:dis "Bravo Chiller 2 Chilled Water Leaving Temperature" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3859-10c4-3901-f23c91a70cca . _:0b111ff8-3859-10c4-3901-f23c91a70cca rdfs:label "" ; _:predictionConf 0.34916172794461753 ; _:sourcePointName "CH2_LeavChwTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0037 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; ph:dis "Bravo Chiller 2 Chilled Water dT (Auto-computed)" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10c5-3902-f23c91a70cca . _:0b111ff8-3859-10c5-3902-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0038 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:chiller, phIoT:cur, phIoT:his, phIoT:leaving, phIoT:point, phIoT:sp, phScience:temp, phScience:water ; rdfs:label "Bravo Chiller 2 Chiller 2 Setpoint" ; ph:dis "Bravo Chiller 2 Chiller 2 Setpoint" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3859-10c6-3903-f23c91a70cca . _:0b111ff8-3859-10c6-3903-f23c91a70cca rdfs:label "" ; _:predictionConf 0.42372423437084655 ; _:sourcePointName "CH2_CHW_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0039 a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Act. Capacity" ; ph:dis "Bravo Chiller 2 Chiller Act. Capacity" ; phIoT:equipRef _:b-0034 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3859-10c7-3904-f23c91a70cca . _:0b111ff8-3859-10c7-3904-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-003a a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cmd, phIoT:cur, phIoT:his, phIoT:point, phIoT:run ; rdfs:label "Bravo Chiller 2 Chiller Enable" ; ph:dis "Bravo Chiller 2 Chiller Enable" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10c8-3905-f23c91a70cca . _:0b111ff8-3859-10c8-3905-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2769995097894551 ; _:sourcePointName "CH2_Clr1Cmd" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-003b a phIoT:chiller, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chiller, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Chiller 2 Chiller Status" ; ph:dis "Bravo Chiller 2 Chiller Status" ; phIoT:equipRef _:b-0034 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0017 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10c9-3906-f23c91a70cca . _:0b111ff8-3859-10c9-3906-f23c91a70cca rdfs:label "" ; _:predictionConf 0.33026119584467384 ; _:sourcePointName "CH2_ChlrSts" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-003c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-1" ; ph:dis "Bravo EF-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-003d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-1 Exhaust Fan Enable" ; ph:dis "Bravo EF-1 Exhaust Fan Enable" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10ca-3907-f23c91a70cca . _:0b111ff8-3859-10ca-3907-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-003e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-1 Exhaust Fan Status" ; ph:dis "Bravo EF-1 Exhaust Fan Status" ; phIoT:equipRef _:b-003c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10cb-3908-f23c91a70cca . _:0b111ff8-3859-10cb-3908-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-003f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-10" ; ph:dis "Bravo EF-10" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0040 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-10 Exhaust Fan Enable" ; ph:dis "Bravo EF-10 Exhaust Fan Enable" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10cc-3909-f23c91a70cca . _:0b111ff8-3859-10cc-3909-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0041 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-10 Exhaust Fan Status" ; ph:dis "Bravo EF-10 Exhaust Fan Status" ; phIoT:equipRef _:b-003f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3859-10cd-390a-f23c91a70cca . _:0b111ff8-3859-10cd-390a-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-06-23T01:00:04.326-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0042 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-11" ; ph:dis "Bravo EF-11" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0043 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-11 Exhaust Fan Enable" ; ph:dis "Bravo EF-11 Exhaust Fan Enable" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3868-5300-390b-f23c91a70cca . _:0b111ff8-3868-5300-390b-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0044 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-11 Exhaust Fan Status" ; ph:dis "Bravo EF-11 Exhaust Fan Status" ; phIoT:equipRef _:b-0042 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3868-5301-390c-f23c91a70cca . _:0b111ff8-3868-5301-390c-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0045 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-12" ; ph:dis "Bravo EF-12" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0046 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-12 Exhaust Fan Enable" ; ph:dis "Bravo EF-12 Exhaust Fan Enable" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3868-5302-390d-f23c91a70cca . _:0b111ff8-3868-5302-390d-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0047 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-12 Exhaust Fan Status" ; ph:dis "Bravo EF-12 Exhaust Fan Status" ; phIoT:equipRef _:b-0045 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c0-390e-f23c91a70cca . _:0b111ff8-3896-19c0-390e-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0048 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-13" ; ph:dis "Bravo EF-13" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0049 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-13 Exhaust Fan Enable" ; ph:dis "Bravo EF-13 Exhaust Fan Enable" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c1-390f-f23c91a70cca . _:0b111ff8-3896-19c1-390f-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-13 Exhaust Fan Status" ; ph:dis "Bravo EF-13 Exhaust Fan Status" ; phIoT:equipRef _:b-0048 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c2-3910-f23c91a70cca . _:0b111ff8-3896-19c2-3910-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004b a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-14" ; ph:dis "Bravo EF-14" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-14 Exhaust Fan Enable" ; ph:dis "Bravo EF-14 Exhaust Fan Enable" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c3-3911-f23c91a70cca . _:0b111ff8-3896-19c3-3911-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-004d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-14 Exhaust Fan Status" ; ph:dis "Bravo EF-14 Exhaust Fan Status" ; phIoT:equipRef _:b-004b ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c4-3912-f23c91a70cca . _:0b111ff8-3896-19c4-3912-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-004e a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-15" ; ph:dis "Bravo EF-15" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-004f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-15 Exhaust Fan Enable" ; ph:dis "Bravo EF-15 Exhaust Fan Enable" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3896-19c5-3913-f23c91a70cca . _:0b111ff8-3896-19c5-3913-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0050 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-15 Exhaust Fan Status" ; ph:dis "Bravo EF-15 Exhaust Fan Status" ; phIoT:equipRef _:b-004e ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c00-3914-f23c91a70cca . _:0b111ff8-38a5-5c00-3914-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0051 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-16" ; ph:dis "Bravo EF-16" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0052 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-16 Exhaust Fan Enable" ; ph:dis "Bravo EF-16 Exhaust Fan Enable" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c01-3915-f23c91a70cca . _:0b111ff8-38a5-5c01-3915-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0053 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-16 Exhaust Fan Status" ; ph:dis "Bravo EF-16 Exhaust Fan Status" ; phIoT:equipRef _:b-0051 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c02-3916-f23c91a70cca . _:0b111ff8-38a5-5c02-3916-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0054 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-17" ; ph:dis "Bravo EF-17" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0055 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-17 Exhaust Fan Enable" ; ph:dis "Bravo EF-17 Exhaust Fan Enable" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c03-3917-f23c91a70cca . _:0b111ff8-38a5-5c03-3917-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0056 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-17 Exhaust Fan Status" ; ph:dis "Bravo EF-17 Exhaust Fan Status" ; phIoT:equipRef _:b-0054 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c04-3918-f23c91a70cca . _:0b111ff8-38a5-5c04-3918-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0057 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-18" ; ph:dis "Bravo EF-18" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0058 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Enable" ; ph:dis "Bravo EF-18 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0057 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c05-3919-f23c91a70cca . _:0b111ff8-38a5-5c05-3919-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0059 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-18 Exhaust Fan Status" ; ph:dis "Bravo EF-18 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0057 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c06-391a-f23c91a70cca . _:0b111ff8-38a5-5c06-391a-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-005a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-19" ; ph:dis "Bravo EF-19" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Enable" ; ph:dis "Bravo EF-19 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-005a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c07-391b-f23c91a70cca . _:0b111ff8-38a5-5c07-391b-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-005c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-19 Exhaust Fan Status" ; ph:dis "Bravo EF-19 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-005a ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c08-391c-f23c91a70cca . _:0b111ff8-38a5-5c08-391c-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-005d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-2" ; ph:dis "Bravo EF-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-005e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-2 Exhaust Fan Enable" ; ph:dis "Bravo EF-2 Exhaust Fan Enable" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c09-391d-f23c91a70cca . _:0b111ff8-38a5-5c09-391d-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-005f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-2 Exhaust Fan Status" ; ph:dis "Bravo EF-2 Exhaust Fan Status" ; phIoT:equipRef _:b-005d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c0a-391e-f23c91a70cca . _:0b111ff8-38a5-5c0a-391e-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0060 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-20" ; ph:dis "Bravo EF-20" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0061 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-20 Exhaust Fan Enable" ; ph:dis "Bravo EF-20 Exhaust Fan Enable" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c0b-391f-f23c91a70cca . _:0b111ff8-38a5-5c0b-391f-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0062 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-20 Exhaust Fan Status" ; ph:dis "Bravo EF-20 Exhaust Fan Status" ; phIoT:equipRef _:b-0060 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38a5-5c0c-3920-f23c91a70cca . _:0b111ff8-38a5-5c0c-3920-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0063 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-21" ; ph:dis "Bravo EF-21" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0064 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Enable" ; ph:dis "Bravo EF-21 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0063 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e40-3921-f23c91a70cca . _:0b111ff8-38b4-9e40-3921-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0065 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-21 Exhaust Fan Status" ; ph:dis "Bravo EF-21 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0063 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e41-3922-f23c91a70cca . _:0b111ff8-38b4-9e41-3922-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0066 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-22" ; ph:dis "Bravo EF-22" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0067 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Enable" ; ph:dis "Bravo EF-22 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-0066 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e42-3923-f23c91a70cca . _:0b111ff8-38b4-9e42-3923-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0068 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-22 Exhaust Fan Status" ; ph:dis "Bravo EF-22 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-0066 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e43-3924-f23c91a70cca . _:0b111ff8-38b4-9e43-3924-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0069 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-23" ; ph:dis "Bravo EF-23" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-23 Exhaust Fan Enable" ; ph:dis "Bravo EF-23 Exhaust Fan Enable" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e44-3925-f23c91a70cca . _:0b111ff8-38b4-9e44-3925-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23SS" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-006b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-23 Exhaust Fan Status" ; ph:dis "Bravo EF-23 Exhaust Fan Status" ; phIoT:equipRef _:b-0069 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e45-3926-f23c91a70cca . _:0b111ff8-38b4-9e45-3926-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF23Status" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-24" ; ph:dis "Bravo EF-24" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-006d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-24 Exhaust Fan Enable" ; ph:dis "Bravo EF-24 Exhaust Fan Enable" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e46-3927-f23c91a70cca . _:0b111ff8-38b4-9e46-3927-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-006e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-24 Exhaust Fan Status" ; ph:dis "Bravo EF-24 Exhaust Fan Status" ; phIoT:equipRef _:b-006c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e47-3928-f23c91a70cca . _:0b111ff8-38b4-9e47-3928-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-006f a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-25" ; ph:dis "Bravo EF-25" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0070 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Enable" ; ph:dis "Bravo EF-25 Exhaust Fan Enable" ; ph:enum "STOP,On" ; phIoT:equipRef _:b-006f ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e48-3929-f23c91a70cca . _:0b111ff8-38b4-9e48-3929-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0071 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-25 Exhaust Fan Status" ; ph:dis "Bravo EF-25 Exhaust Fan Status" ; ph:enum "stateNul,Off,RUNNING" ; phIoT:equipRef _:b-006f ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e49-392a-f23c91a70cca . _:0b111ff8-38b4-9e49-392a-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0072 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-26" ; ph:dis "Bravo EF-26" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0073 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-26 Exhaust Fan Enable" ; ph:dis "Bravo EF-26 Exhaust Fan Enable" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e4a-392b-f23c91a70cca . _:0b111ff8-38b4-9e4a-392b-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0074 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-26 Exhaust Fan Status" ; ph:dis "Bravo EF-26 Exhaust Fan Status" ; phIoT:equipRef _:b-0072 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e4b-392c-f23c91a70cca . _:0b111ff8-38b4-9e4b-392c-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0075 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-27" ; ph:dis "Bravo EF-27" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0076 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-27 Exhaust Fan Enable" ; ph:dis "Bravo EF-27 Exhaust Fan Enable" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e4c-392d-f23c91a70cca . _:0b111ff8-38b4-9e4c-392d-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0077 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-27 Exhaust Fan Status" ; ph:dis "Bravo EF-27 Exhaust Fan Status" ; phIoT:equipRef _:b-0075 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e4d-392e-f23c91a70cca . _:0b111ff8-38b4-9e4d-392e-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0078 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-28" ; ph:dis "Bravo EF-28" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0079 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-28 Exhaust Fan Status" ; ph:dis "Bravo EF-28 Exhaust Fan Status" ; phIoT:equipRef _:b-0078 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38b4-9e4e-392f-f23c91a70cca . _:0b111ff8-38b4-9e4e-392f-f23c91a70cca rdfs:label "" ; _:sourcePointName "EF28Status" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-007a a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-3" ; ph:dis "Bravo EF-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-3 Exhaust Fan Enable" ; ph:dis "Bravo EF-3 Exhaust Fan Enable" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e080-3930-f23c91a70cca . _:0b111ff8-38c3-e080-3930-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-007c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-3 Exhaust Fan Status" ; ph:dis "Bravo EF-3 Exhaust Fan Status" ; phIoT:equipRef _:b-007a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e081-3931-f23c91a70cca . _:0b111ff8-38c3-e081-3931-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFStatus" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-007d a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-4" ; ph:dis "Bravo EF-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-007e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-4 Exhaust Fan Enable" ; ph:dis "Bravo EF-4 Exhaust Fan Enable" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e082-3932-f23c91a70cca . _:0b111ff8-38c3-e082-3932-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-007f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-4 Exhaust Fan Status" ; ph:dis "Bravo EF-4 Exhaust Fan Status" ; phIoT:equipRef _:b-007d ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e083-3933-f23c91a70cca . _:0b111ff8-38c3-e083-3933-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0080 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-5" ; ph:dis "Bravo EF-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0081 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-5 Exhaust Fan Enable" ; ph:dis "Bravo EF-5 Exhaust Fan Enable" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e084-3934-f23c91a70cca . _:0b111ff8-38c3-e084-3934-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0082 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-5 Exhaust Fan Status" ; ph:dis "Bravo EF-5 Exhaust Fan Status" ; phIoT:equipRef _:b-0080 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e085-3935-f23c91a70cca . _:0b111ff8-38c3-e085-3935-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0083 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-6" ; ph:dis "Bravo EF-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0084 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-6 Exhaust Fan Enable" ; ph:dis "Bravo EF-6 Exhaust Fan Enable" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e086-3936-f23c91a70cca . _:0b111ff8-38c3-e086-3936-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0085 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-6 Exhaust Fan Status" ; ph:dis "Bravo EF-6 Exhaust Fan Status" ; phIoT:equipRef _:b-0083 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e087-3937-f23c91a70cca . _:0b111ff8-38c3-e087-3937-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-05-28T01:00:09.102-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0086 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-7" ; ph:dis "Bravo EF-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-0087 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-7 Exhaust Fan Enable" ; ph:dis "Bravo EF-7 Exhaust Fan Enable" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e088-3938-f23c91a70cca . _:0b111ff8-38c3-e088-3938-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0088 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-7 Exhaust Fan Status" ; ph:dis "Bravo EF-7 Exhaust Fan Status" ; phIoT:equipRef _:b-0086 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e089-3939-f23c91a70cca . _:0b111ff8-38c3-e089-3939-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.929-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-0089 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-8" ; ph:dis "Bravo EF-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-8 Exhaust Fan Enable" ; ph:dis "Bravo EF-8 Exhaust Fan Enable" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-38c3-e08a-393a-f23c91a70cca . _:0b111ff8-38c3-e08a-393a-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-008b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-8 Exhaust Fan Status" ; ph:dis "Bravo EF-8 Exhaust Fan Status" ; phIoT:equipRef _:b-0089 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3900-e980-393b-f23c91a70cca . _:0b111ff8-3900-e980-393b-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-11T13:56:25.945-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" . _:b-008c a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:fan, phIoT:hvac ; rdfs:label "Bravo EF-9" ; ph:dis "Bravo EF-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 . _:b-008d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point ; rdfs:label "Bravo EF-9 Exhaust Fan Enable" ; ph:dis "Bravo EF-9 Exhaust Fan Enable" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3900-e981-393c-f23c91a70cca . _:0b111ff8-3900-e981-393c-f23c91a70cca rdfs:label "" ; _:sourcePointName "EFSS" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-008e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:exhaust, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo EF-9 Exhaust Fan Status" ; ph:dis "Bravo EF-9 Exhaust Fan Status" ; phIoT:equipRef _:b-008c ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a4 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3900-e982-393d-f23c91a70cca . _:0b111ff8-3900-e982-393d-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-07-02T01:00:04.305-04:00"^^xsd:dateTime ; _:sourcePointName "EFStatus" ; _:dataSyncType "error" ; _:pointType "" . _:b-008f a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-1" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0090 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-1 Cooling Valve Output" ; ph:dis "Bravo FCU-1 Cooling Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3900-e983-393e-f23c91a70cca . _:0b111ff8-3900-e983-393e-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0091 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-1 Heating Valve Output" ; ph:dis "Bravo FCU-1 Heating Valve Output" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3900-e984-393f-f23c91a70cca . _:0b111ff8-3900-e984-393f-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0092 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature" ; ph:dis "Bravo FCU-1 Zone Temperature" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3900-e985-3940-f23c91a70cca . _:0b111ff8-3900-e985-3940-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0093 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-1 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-1 Zone Temperature Setpoint" ; phIoT:equipRef _:b-008f ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3900-e986-3941-f23c91a70cca . _:0b111ff8-3900-e986-3941-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0094 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-2" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-0095 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-2 Cooling Valve Output" ; ph:dis "Bravo FCU-2 Cooling Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3900-e987-3942-f23c91a70cca . _:0b111ff8-3900-e987-3942-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0096 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-2 Heating Valve Output" ; ph:dis "Bravo FCU-2 Heating Valve Output" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3900-e988-3943-f23c91a70cca . _:0b111ff8-3900-e988-3943-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0097 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature" ; ph:dis "Bravo FCU-2 Zone Temperature" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3900-e989-3944-f23c91a70cca . _:0b111ff8-3900-e989-3944-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0098 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-2 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-2 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0094 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3900-e98a-3945-f23c91a70cca . _:0b111ff8-3900-e98a-3945-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0099 a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-3" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-3 Cooling Valve Output" ; ph:dis "Bravo FCU-3 Cooling Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3910-2bc0-3946-f23c91a70cca . _:0b111ff8-3910-2bc0-3946-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-009b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-3 Heating Valve Output" ; ph:dis "Bravo FCU-3 Heating Valve Output" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3910-2bc1-3947-f23c91a70cca . _:0b111ff8-3910-2bc1-3947-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature" ; ph:dis "Bravo FCU-3 Zone Temperature" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3910-2bc2-3948-f23c91a70cca . _:0b111ff8-3910-2bc2-3948-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-009d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-3 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-3 Zone Temperature Setpoint" ; phIoT:equipRef _:b-0099 ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3910-2bc3-3949-f23c91a70cca . _:0b111ff8-3910-2bc3-3949-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-009e a phIoT:fcu, phIoT:thermostat ; ph:hasTag phIoT:chilledWaterCooling, phIoT:directZone, phIoT:elecHeating, phIoT:equip, phIoT:fcu, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:zone ; rdfs:label "Bravo FCU-4" ; phIoT:chilledWaterRef _:b-001e ; ph:dis "Bravo FCU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 . _:b-009f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve, phScience:water ; rdfs:label "Bravo FCU-4 Cooling Valve Output" ; ph:dis "Bravo FCU-4 Cooling Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3910-2bc4-394a-f23c91a70cca . _:0b111ff8-3910-2bc4-394a-f23c91a70cca rdfs:label "" ; _:sourcePointName "ChwVlv" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:heat, phIoT:his, phIoT:point, phIoT:sensor, phIoT:valve ; rdfs:label "Bravo FCU-4 Heating Valve Output" ; ph:dis "Bravo FCU-4 Heating Valve Output" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3910-2bc5-394b-f23c91a70cca . _:0b111ff8-3910-2bc5-394b-f23c91a70cca rdfs:label "" ; _:precision 0 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature" ; ph:dis "Bravo FCU-4 Zone Temperature" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3910-2bc6-394c-f23c91a70cca . _:0b111ff8-3910-2bc6-394c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpcTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo FCU-4 Zone Temperature Setpoint" ; ph:dis "Bravo FCU-4 Zone Temperature Setpoint" ; phIoT:equipRef _:b-009e ; ph:kind "Number" ; ph:maxVal 327 ; ph:minVal -273 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00a3 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3910-2bc7-394d-f23c91a70cca . _:0b111ff8-3910-2bc7-394d-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00a3 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo FCUs" ; ph:dis "Bravo FCUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3910-2bc8-394e-f23c91a70cca . _:0b111ff8-3910-2bc8-394e-f23c91a70cca rdfs:label "" . _:b-00a4 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Fans" ; ph:dis "Bravo Fans" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3910-2bc9-394f-f23c91a70cca . _:0b111ff8-3910-2bc9-394f-f23c91a70cca rdfs:label "" . _:b-00a5 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 1" ; ph:dis "Bravo HHW Pump 1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump Status" ; ph:dis "Bravo HHW Pump 1 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a5 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-3910-2bca-3950-f23c91a70cca . _:0b111ff8-3910-2bca-3950-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 1 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 1 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-3910-2bcb-3951-f23c91a70cca . _:0b111ff8-3910-2bcb-3951-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00a8 a phIoT:equip ; ph:hasTag phIoT:equip, phIoT:hot, phIoT:hvac, phIoT:pump, phScience:water ; rdfs:label "Bravo HHW Pump 2" ; ph:dis "Bravo HHW Pump 2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab . _:b-00a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump Status" ; ph:dis "Bravo HHW Pump 2 HHW Pump Status" ; ph:enum "false,true" ; phIoT:equipRef _:b-00a8 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-3910-2bcc-3952-f23c91a70cca . _:0b111ff8-3910-2bcc-3952-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cur, phIoT:his, phIoT:hot, phIoT:point, phIoT:pump, phIoT:sensor, phScience:speed, phScience:water ; rdfs:label "Bravo HHW Pump 2 HHW Pump VFD Speed" ; ph:dis "Bravo HHW Pump 2 HHW Pump VFD Speed" ; phIoT:equipRef _:b-00a8 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-00ab ; ph:tz "Chicago" ; _:custom _:0b111ff8-3910-2bcd-3953-f23c91a70cca . _:0b111ff8-3910-2bcd-3953-f23c91a70cca rdfs:label "" ; _:precision 2 ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00ab a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo HW System" ; ph:dis "Bravo HW System" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3910-2bce-3954-f23c91a70cca . _:0b111ff8-3910-2bce-3954-f23c91a70cca rdfs:label "" . _:b-00ac a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-1" ; ph:dis "Bravo RTU-1" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0b111ff8-3910-2bcf-3955-f23c91a70cca . _:0b111ff8-3910-2bcf-3955-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15300 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 145 ; _:designOutsideAirFlowMin 3500 ; _:designDischargeFanAirDeltaPressure 7.04 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59 ; _:designChilledWaterPower 722.3 ; _:designHotWaterFlow 24.1 ; _:designChilledWaterFlow 96.4 ; _:designReturnAirFlow 15300 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 15300 ; _:designReturnFanPower 15 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.66 . _:b-00ad a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 AHU Operation Mode" ; ph:dis "Bravo RTU-1 AHU Operation Mode" ; phIoT:equipRef _:b-00ac ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3910-2bd0-3956-f23c91a70cca . _:0b111ff8-3910-2bd0-3956-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-1 Cooling Valve Output" ; ph:dis "Bravo RTU-1 Cooling Valve Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3910-2bd1-3957-f23c91a70cca . _:0b111ff8-3910-2bd1-3957-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-1 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-391f-6e00-3958-f23c91a70cca . _:0b111ff8-391f-6e00-3958-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-1 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-391f-6e01-3959-f23c91a70cca . _:0b111ff8-391f-6e01-3959-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00b1 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-1 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0b111ff8-392e-b040-395a-f23c91a70cca . _:0b111ff8-392e-b040-395a-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-1 Humidifier Enable" ; ph:dis "Bravo RTU-1 Humidifier Enable" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-392e-b041-395b-f23c91a70cca . _:0b111ff8-392e-b041-395b-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-1 Humidifier Output" ; ph:dis "Bravo RTU-1 Humidifier Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-392e-b042-395c-f23c91a70cca . _:0b111ff8-392e-b042-395c-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00b4 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-1 Max Damper Position" ; ph:dis "Bravo RTU-1 Max Damper Position" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-392e-b043-395d-f23c91a70cca . _:0b111ff8-392e-b043-395d-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-392e-b044-395e-f23c91a70cca . _:0b111ff8-392e-b044-395e-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime ; _:pointType "" . _:b-00b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-1 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-392e-b045-395f-f23c91a70cca . _:0b111ff8-392e-b045-395f-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-392e-b046-3960-f23c91a70cca . _:0b111ff8-392e-b046-3960-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature" ; ph:dis "Bravo RTU-1 Mixed Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-393d-f280-3961-f23c91a70cca . _:0b111ff8-393d-f280-3961-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-393d-f281-3962-f23c91a70cca . _:0b111ff8-393d-f281-3962-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-1 Outside Air Damper Output" ; ph:dis "Bravo RTU-1 Outside Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f282-3963-f23c91a70cca . _:0b111ff8-393d-f282-3963-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Outside Air Flow" ; ph:dis "Bravo RTU-1 Outside Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-393d-f283-3964-f23c91a70cca . _:0b111ff8-393d-f283-3964-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00bc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-1 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-393d-f284-3965-f23c91a70cca . _:0b111ff8-393d-f284-3965-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.656-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00bd a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Percent Outside Air" ; ph:dis "Bravo RTU-1 Percent Outside Air" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f285-3966-f23c91a70cca . _:0b111ff8-393d-f285-3966-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Damper Output" ; ph:dis "Bravo RTU-1 Return Air Damper Output" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f286-3967-f23c91a70cca . _:0b111ff8-393d-f286-3967-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Flow" ; ph:dis "Bravo RTU-1 Return Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-393d-f287-3968-f23c91a70cca . _:0b111ff8-393d-f287-3968-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Air Humidity" ; ph:dis "Bravo RTU-1 Return Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f288-3969-f23c91a70cca . _:0b111ff8-393d-f288-3969-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-00c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Return Air Temperature" ; ph:dis "Bravo RTU-1 Return Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-393d-f289-396a-f23c91a70cca . _:0b111ff8-393d-f289-396a-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Return Fan Status" ; ph:dis "Bravo RTU-1 Return Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-393d-f28a-396b-f23c91a70cca . _:0b111ff8-393d-f28a-396b-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-1 Return Fan VFD Speed" ; ph:dis "Bravo RTU-1 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f28b-396c-f23c91a70cca . _:0b111ff8-393d-f28b-396c-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Flow" ; ph:dis "Bravo RTU-1 Supply Air Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-393d-f28c-396d-f23c91a70cca . _:0b111ff8-393d-f28c-396d-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Humidity" ; ph:dis "Bravo RTU-1 Supply Air Humidity" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f28d-396e-f23c91a70cca . _:0b111ff8-393d-f28d-396e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-393d-f28e-396f-f23c91a70cca . _:0b111ff8-393d-f28e-396f-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-1 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-393d-f28f-3970-f23c91a70cca . _:0b111ff8-393d-f28f-3970-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Air Static Pressure" ; ph:dis "Bravo RTU-1 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-393d-f290-3971-f23c91a70cca . _:0b111ff8-393d-f290-3971-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00c9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature" ; ph:dis "Bravo RTU-1 Supply Air Temperature" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-393d-f291-3972-f23c91a70cca . _:0b111ff8-393d-f291-3972-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-1 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-1 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-393d-f292-3973-f23c91a70cca . _:0b111ff8-393d-f292-3973-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-1 Supply Fan Status" ; ph:dis "Bravo RTU-1 Supply Fan Status" ; phIoT:equipRef _:b-00ac ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-394d-34c0-3974-f23c91a70cca . _:0b111ff8-394d-34c0-3974-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00cc a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-1 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-1 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-394d-34c1-3975-f23c91a70cca . _:0b111ff8-394d-34c1-3975-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00cd a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-1 VAV Total Flow" ; ph:dis "Bravo RTU-1 VAV Total Flow" ; phIoT:equipRef _:b-00ac ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-394d-34c2-3976-f23c91a70cca . _:0b111ff8-394d-34c2-3976-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00ce a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-2" ; ph:dis "Bravo RTU-2" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0b111ff8-394d-34c3-3977-f23c91a70cca . _:0b111ff8-394d-34c3-3977-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 30000 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 288 ; _:designOutsideAirFlowMin 6750 ; _:designDischargeFanAirDeltaPressure 6.4 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 59.2 ; _:designChilledWaterPower 1225.8 ; _:designHotWaterFlow 48 ; _:designChilledWaterFlow 160.9 ; _:designReturnAirFlow 30000 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 30000 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 50 ; _:designReturnFanAirDeltaPressure 1.62 . _:b-00cf a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 AHU Operation Mode" ; ph:dis "Bravo RTU-2 AHU Operation Mode" ; phIoT:equipRef _:b-00ce ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-394d-34c4-3978-f23c91a70cca . _:0b111ff8-394d-34c4-3978-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-2 Calculated Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-394d-34c5-3979-f23c91a70cca . _:0b111ff8-394d-34c5-3979-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3970116854281743 ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-2 Cooling Valve Output" ; ph:dis "Bravo RTU-2 Cooling Valve Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-394d-34c6-397a-f23c91a70cca . _:0b111ff8-394d-34c6-397a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-2 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-394d-34c7-397b-f23c91a70cca . _:0b111ff8-394d-34c7-397b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d3 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-2 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-394d-34c8-397c-f23c91a70cca . _:0b111ff8-394d-34c8-397c-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00d4 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-2 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0b111ff8-394d-34c9-397d-f23c91a70cca . _:0b111ff8-394d-34c9-397d-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-2 Humidifier Enable" ; ph:dis "Bravo RTU-2 Humidifier Enable" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-394d-34ca-397e-f23c91a70cca . _:0b111ff8-394d-34ca-397e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-2 Humidifier Output" ; ph:dis "Bravo RTU-2 Humidifier Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-394d-34cb-397f-f23c91a70cca . _:0b111ff8-394d-34cb-397f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00d7 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-2 Max Damper Position" ; ph:dis "Bravo RTU-2 Max Damper Position" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-394d-34cc-3980-f23c91a70cca . _:0b111ff8-394d-34cc-3980-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-2 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-394d-34cd-3981-f23c91a70cca . _:0b111ff8-394d-34cd-3981-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00d9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Min Outdoor Air Flow" ; ph:dis "Bravo RTU-2 Min Outdoor Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-394d-34ce-3982-f23c91a70cca . _:0b111ff8-394d-34ce-3982-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:predictionConf 0.5591032698291575 ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-7700-3983-f23c91a70cca . _:0b111ff8-395c-7700-3983-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature" ; ph:dis "Bravo RTU-2 Mixed Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-395c-7701-3984-f23c91a70cca . _:0b111ff8-395c-7701-3984-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-395c-7702-3985-f23c91a70cca . _:0b111ff8-395c-7702-3985-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-2 Outside Air Damper Output" ; ph:dis "Bravo RTU-2 Outside Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-7703-3986-f23c91a70cca . _:0b111ff8-395c-7703-3986-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-00de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Outside Air Flow" ; ph:dis "Bravo RTU-2 Outside Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-395c-7704-3987-f23c91a70cca . _:0b111ff8-395c-7704-3987-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00df a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-2 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-395c-7705-3988-f23c91a70cca . _:0b111ff8-395c-7705-3988-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00e0 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Percent Outside Air" ; ph:dis "Bravo RTU-2 Percent Outside Air" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-7706-3989-f23c91a70cca . _:0b111ff8-395c-7706-3989-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00e1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Damper Output" ; ph:dis "Bravo RTU-2 Return Air Damper Output" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-7707-398a-f23c91a70cca . _:0b111ff8-395c-7707-398a-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Flow" ; ph:dis "Bravo RTU-2 Return Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-395c-7708-398b-f23c91a70cca . _:0b111ff8-395c-7708-398b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Air Humidity" ; ph:dis "Bravo RTU-2 Return Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-7709-398c-f23c91a70cca . _:0b111ff8-395c-7709-398c-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Return Air Temperature" ; ph:dis "Bravo RTU-2 Return Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-395c-770a-398d-f23c91a70cca . _:0b111ff8-395c-770a-398d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Return Fan Status" ; ph:dis "Bravo RTU-2 Return Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-395c-770b-398e-f23c91a70cca . _:0b111ff8-395c-770b-398e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-00e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Return Fan VFD Speed" ; ph:dis "Bravo RTU-2 Return Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-770c-398f-f23c91a70cca . _:0b111ff8-395c-770c-398f-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-00e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Flow" ; ph:dis "Bravo RTU-2 Supply Air Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-395c-770d-3990-f23c91a70cca . _:0b111ff8-395c-770d-3990-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Humidity" ; ph:dis "Bravo RTU-2 Supply Air Humidity" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-395c-770e-3991-f23c91a70cca . _:0b111ff8-395c-770e-3991-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-00e9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3999-8000-3992-f23c91a70cca . _:0b111ff8-3999-8000-3992-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7045004074770955 ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-00ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-3999-8001-3993-f23c91a70cca . _:0b111ff8-3999-8001-3993-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-00eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Static Pressure Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-3999-8002-3994-f23c91a70cca . _:0b111ff8-3999-8002-3994-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-00ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature" ; ph:dis "Bravo RTU-2 Supply Air Temperature" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3999-8003-3995-f23c91a70cca . _:0b111ff8-3999-8003-3995-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-2 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-2 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3999-8004-3996-f23c91a70cca . _:0b111ff8-3999-8004-3996-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-00ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-2 Supply Fan Status" ; ph:dis "Bravo RTU-2 Supply Fan Status" ; phIoT:equipRef _:b-00ce ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3999-8005-3997-f23c91a70cca . _:0b111ff8-3999-8005-3997-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-00ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-2 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-2 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3999-8006-3998-f23c91a70cca . _:0b111ff8-3999-8006-3998-f23c91a70cca rdfs:label "" ; _:predictionConf 0.13813130060214382 ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-00f0 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-2 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-2 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3999-8007-3999-f23c91a70cca . _:0b111ff8-3999-8007-3999-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f1 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-2 VAV Total Flow" ; ph:dis "Bravo RTU-2 VAV Total Flow" ; phIoT:equipRef _:b-00ce ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3999-8008-399a-f23c91a70cca . _:0b111ff8-3999-8008-399a-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f2 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-3" ; ph:dis "Bravo RTU-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0b111ff8-3999-8009-399b-f23c91a70cca . _:0b111ff8-3999-8009-399b-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 33600 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 318 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 6.7 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1346.1 ; _:designHotWaterFlow 53 ; _:designChilledWaterFlow 180.2 ; _:designReturnAirFlow 33600 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 33600 ; _:designReturnFanPower 25 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 60 ; _:designReturnFanAirDeltaPressure 1.63 . _:b-00f3 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 AHU Operation Mode" ; ph:dis "Bravo RTU-3 AHU Operation Mode" ; phIoT:equipRef _:b-00f2 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39a8-c240-399c-f23c91a70cca . _:0b111ff8-39a8-c240-399c-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-3 Cooling Valve Output" ; ph:dis "Bravo RTU-3 Cooling Valve Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39a8-c241-399d-f23c91a70cca . _:0b111ff8-39a8-c241-399d-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5846394026860828 ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-3 Exhaust Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39a8-c242-399e-f23c91a70cca . _:0b111ff8-39a8-c242-399e-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6232903565384572 ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00f6 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-3 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39a8-c243-399f-f23c91a70cca . _:0b111ff8-39a8-c243-399f-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-00f7 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-3 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0b111ff8-39a8-c244-39a0-f23c91a70cca . _:0b111ff8-39a8-c244-39a0-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-3 Humidifier Enable" ; ph:dis "Bravo RTU-3 Humidifier Enable" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39a8-c245-39a1-f23c91a70cca . _:0b111ff8-39a8-c245-39a1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2169429859073283 ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-00f9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-3 Humidifier Output" ; ph:dis "Bravo RTU-3 Humidifier Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39a8-c246-39a2-f23c91a70cca . _:0b111ff8-39a8-c246-39a2-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7439557600414519 ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-00fa a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-3 Max Damper Position" ; ph:dis "Bravo RTU-3 Max Damper Position" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39a8-c247-39a3-f23c91a70cca . _:0b111ff8-39a8-c247-39a3-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-00fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Min OA Flow Setpoint" ; ph:dis "Bravo RTU-3 Min OA Flow Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39c7-46c0-39a4-f23c91a70cca . _:0b111ff8-39c7-46c0-39a4-f23c91a70cca rdfs:label "" ; _:predictionConf 0.2305698711556413 ; _:sourcePointName "MINOASTPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-00fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39c7-46c1-39a5-f23c91a70cca . _:0b111ff8-39c7-46c1-39a5-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7226466689139898 ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-00fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature" ; ph:dis "Bravo RTU-3 Mixed Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39c7-46c2-39a6-f23c91a70cca . _:0b111ff8-39c7-46c2-39a6-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5092275130999935 ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-00fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39c7-46c3-39a7-f23c91a70cca . _:0b111ff8-39c7-46c3-39a7-f23c91a70cca rdfs:label "" ; _:predictionConf 0.41409123546331406 ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-00ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-3 Outside Air Damper Output" ; ph:dis "Bravo RTU-3 Outside Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39c7-46c4-39a8-f23c91a70cca . _:0b111ff8-39c7-46c4-39a8-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7395401248861597 ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0100 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Outside Air Flow" ; ph:dis "Bravo RTU-3 Outside Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39d6-8900-39a9-f23c91a70cca . _:0b111ff8-39d6-8900-39a9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7870789837941534 ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0101 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-3 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39d6-8901-39aa-f23c91a70cca . _:0b111ff8-39d6-8901-39aa-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0102 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Percent Outside Air" ; ph:dis "Bravo RTU-3 Percent Outside Air" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39d6-8902-39ab-f23c91a70cca . _:0b111ff8-39d6-8902-39ab-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0103 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return ; rdfs:label "Bravo RTU-3 Return Air Damper Output" ; ph:dis "Bravo RTU-3 Return Air Damper Output" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39d6-8903-39ac-f23c91a70cca . _:0b111ff8-39d6-8903-39ac-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3561100767369028 ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0104 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Flow" ; ph:dis "Bravo RTU-3 Return Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39d6-8904-39ad-f23c91a70cca . _:0b111ff8-39d6-8904-39ad-f23c91a70cca rdfs:label "" ; _:predictionConf 0.8263008623409421 ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0105 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Air Humidity" ; ph:dis "Bravo RTU-3 Return Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39d6-8905-39ae-f23c91a70cca . _:0b111ff8-39d6-8905-39ae-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7016271134196499 ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0106 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Return Air Temperature" ; ph:dis "Bravo RTU-3 Return Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39d6-8906-39af-f23c91a70cca . _:0b111ff8-39d6-8906-39af-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5745623242771728 ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0107 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Return Fan Status" ; ph:dis "Bravo RTU-3 Return Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39d6-8907-39b0-f23c91a70cca . _:0b111ff8-39d6-8907-39b0-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5721715629985896 ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0108 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Return Fan VFD Speed" ; ph:dis "Bravo RTU-3 Return Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39d6-8908-39b1-f23c91a70cca . _:0b111ff8-39d6-8908-39b1-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3324288739189246 ; _:sourcePointName "RTDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0109 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Flow" ; ph:dis "Bravo RTU-3 Supply Air Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39d6-8909-39b2-f23c91a70cca . _:0b111ff8-39d6-8909-39b2-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7841375570046363 ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-010a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Humidity" ; ph:dis "Bravo RTU-3 Supply Air Humidity" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39d6-890a-39b3-f23c91a70cca . _:0b111ff8-39d6-890a-39b3-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7933659564917551 ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-010b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-3 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-39d6-890b-39b4-f23c91a70cca . _:0b111ff8-39d6-890b-39b4-f23c91a70cca rdfs:label "" ; _:predictionConf 0.48636472322277824 ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-010c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Air Static Pressure" ; ph:dis "Bravo RTU-3 Supply Air Static Pressure" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-39d6-890c-39b5-f23c91a70cca . _:0b111ff8-39d6-890c-39b5-f23c91a70cca rdfs:label "" ; _:predictionConf 0.3539915786588711 ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-010d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature" ; ph:dis "Bravo RTU-3 Supply Air Temperature" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39d6-890d-39b6-f23c91a70cca . _:0b111ff8-39d6-890d-39b6-f23c91a70cca rdfs:label "" ; _:predictionConf 0.5598774100147106 ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-010e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-3 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-3 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39e5-cb40-39b7-f23c91a70cca . _:0b111ff8-39e5-cb40-39b7-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6936845307741977 ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-010f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-3 Supply Fan Status" ; ph:dis "Bravo RTU-3 Supply Fan Status" ; phIoT:equipRef _:b-00f2 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39e5-cb41-39b8-f23c91a70cca . _:0b111ff8-39e5-cb41-39b8-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6818756457191736 ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0110 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-3 Supply Fan VFD Speed" ; ph:dis "Bravo RTU-3 Supply Fan VFD Speed" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb42-39b9-f23c91a70cca . _:0b111ff8-39e5-cb42-39b9-f23c91a70cca rdfs:label "" ; _:predictionConf 0.32036669663302475 ; _:sourcePointName "SPDrvSpd" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0111 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-3 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-3 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39e5-cb43-39ba-f23c91a70cca . _:0b111ff8-39e5-cb43-39ba-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0112 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-3 VAV Total Flow" ; ph:dis "Bravo RTU-3 VAV Total Flow" ; phIoT:equipRef _:b-00f2 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39e5-cb44-39bb-f23c91a70cca . _:0b111ff8-39e5-cb44-39bb-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0113 a phIoT:rtu ; ph:hasTag phIoT:ahu, phIoT:chilledWaterCooling, phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:rtu, phIoT:singleDuct, phIoT:vavZone ; rdfs:label "Bravo RTU-4" ; ph:dis "Bravo RTU-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; _:custom _:0b111ff8-39e5-cb45-39bc-f23c91a70cca . _:0b111ff8-39e5-cb45-39bc-f23c91a70cca rdfs:label "" ; _:designDischargeAirFlow 15700 ; _:designHotWaterLeavingTemp 65 ; _:designHotWaterPower 243 ; _:designOutsideAirFlowMin 7125 ; _:designDischargeFanAirDeltaPressure 4.76 ; _:designSource "Drawings" ; _:designChilledWaterLeavingTemp 58.9 ; _:designChilledWaterPower 1028.7 ; _:designHotWaterFlow 41 ; _:designChilledWaterFlow 137.8 ; _:designReturnAirFlow 25700 ; _:designHotWaterEnteringTemp 75 ; _:designOutsideAirFlow 25700 ; _:designReturnFanPower 20 ; _:designChilledWaterEnteringTemp 44 ; _:designDischargeFanPower 40 ; _:designReturnFanAirDeltaPressure 1.64 . _:b-0114 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:computed, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 AHU Operation Mode" ; ph:dis "Bravo RTU-4 AHU Operation Mode" ; phIoT:equipRef _:b-0113 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39e5-cb46-39bd-f23c91a70cca . _:0b111ff8-39e5-cb46-39bd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0115 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:chilled, phIoT:cmd, phIoT:cool, phIoT:cur, phIoT:his, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo RTU-4 Cooling Valve Output" ; ph:dis "Bravo RTU-4 Cooling Valve Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb47-39be-f23c91a70cca . _:0b111ff8-39e5-cb47-39be-f23c91a70cca rdfs:label "" ; _:sourcePointName "CWV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0116 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:exhaust, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Exhaust Air Damper Output" ; ph:dis "Bravo RTU-4 Exhaust Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb48-39bf-f23c91a70cca . _:0b111ff8-39e5-cb48-39bf-f23c91a70cca rdfs:label "" ; _:sourcePointName "EAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0117 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Fan Power (Auto-computed)" ; ph:dis "Bravo RTU-4 Fan Power (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39e5-cb49-39c0-f23c91a70cca . _:0b111ff8-39e5-cb49-39c0-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0118 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; ph:dis "Bravo RTU-4 Heating/Cooling Load (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "BTU/h" ; _:custom _:0b111ff8-39e5-cb4a-39c1-f23c91a70cca . _:0b111ff8-39e5-cb4a-39c1-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0119 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:enable, phIoT:his, phIoT:humidifier, phIoT:point ; rdfs:label "Bravo RTU-4 Humidifier Enable" ; ph:dis "Bravo RTU-4 Humidifier Enable" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39e5-cb4b-39c2-f23c91a70cca . _:0b111ff8-39e5-cb4b-39c2-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM_ENABLE" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-011a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:his, phIoT:humidifier, phIoT:point, phScience:steam, phIoT:valve ; rdfs:label "Bravo RTU-4 Humidifier Output" ; ph:dis "Bravo RTU-4 Humidifier Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb4c-39c3-f23c91a70cca . _:0b111ff8-39e5-cb4c-39c3-f23c91a70cca rdfs:label "" ; _:sourcePointName "HUM VLV" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-011b a phIoT:computed-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:computed, phIoT:damper, phIoT:his, phIoT:point ; rdfs:label "Bravo RTU-4 Max Damper Position" ; ph:dis "Bravo RTU-4 Max Damper Position" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb4d-39c4-f23c91a70cca . _:0b111ff8-39e5-cb4d-39c4-f23c91a70cca ph:hasTag ph:max ; rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-011c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39e5-cb4e-39c5-f23c91a70cca . _:0b111ff8-39e5-cb4e-39c5-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MinOA_SP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-011d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Min Outdoor Air Flow/10" ; ph:dis "Bravo RTU-4 Min Outdoor Air Flow/10" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39e5-cb4f-39c6-f23c91a70cca . _:0b111ff8-39e5-cb4f-39c6-f23c91a70cca ph:hasTag ph:min ; rdfs:label "" ; _:sourcePointName "MIN OA CFM / 10" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-011e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Minimum Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Minimum Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d80-39c7-f23c91a70cca . _:0b111ff8-39f5-0d80-39c7-f23c91a70cca rdfs:label "" ; _:sourcePointName "Min OAD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-011f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature" ; ph:dis "Bravo RTU-4 Mixed Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39f5-0d81-39c8-f23c91a70cca . _:0b111ff8-39f5-0d81-39c8-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0120 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:mixed, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Mixed Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Mixed Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39f5-0d82-39c9-f23c91a70cca . _:0b111ff8-39f5-0d82-39c9-f23c91a70cca rdfs:label "" ; _:sourcePointName "MAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0121 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:his, phIoT:outside, phIoT:point ; rdfs:label "Bravo RTU-4 Outside Air Damper Output" ; ph:dis "Bravo RTU-4 Outside Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d83-39ca-f23c91a70cca . _:0b111ff8-39f5-0d83-39ca-f23c91a70cca rdfs:label "" ; _:sourcePointName "OAD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0122 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Outside Air Flow" ; ph:dis "Bravo RTU-4 Outside Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39f5-0d84-39cb-f23c91a70cca . _:0b111ff8-39f5-0d84-39cb-f23c91a70cca rdfs:label "" ; _:sourcePointName "OA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0123 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; ph:dis "Bravo RTU-4 Outside Air Percentage (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39f5-0d85-39cc-f23c91a70cca . _:0b111ff8-39f5-0d85-39cc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-04-09T01:00:02.664-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0124 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phIoT:his, phIoT:outside, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Percent Outside Air" ; ph:dis "Bravo RTU-4 Percent Outside Air" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d86-39cd-f23c91a70cca . _:0b111ff8-39f5-0d86-39cd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0125 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:damper, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Damper Output" ; ph:dis "Bravo RTU-4 Return Air Damper Output" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d87-39ce-f23c91a70cca . _:0b111ff8-39f5-0d87-39ce-f23c91a70cca rdfs:label "" ; _:sourcePointName "RET/REL DAMPER" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0126 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phScience:flow, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Flow" ; ph:dis "Bravo RTU-4 Return Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39f5-0d88-39cf-f23c91a70cca . _:0b111ff8-39f5-0d88-39cf-f23c91a70cca rdfs:label "" ; _:sourcePointName "RA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0127 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:return, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Air Humidity" ; ph:dis "Bravo RTU-4 Return Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d89-39d0-f23c91a70cca . _:0b111ff8-39f5-0d89-39d0-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAH" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0128 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Return Air Temperature" ; ph:dis "Bravo RTU-4 Return Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-39f5-0d8a-39d1-f23c91a70cca . _:0b111ff8-39f5-0d8a-39d1-f23c91a70cca rdfs:label "" ; _:sourcePointName "RAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0129 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Return Fan Status" ; ph:dis "Bravo RTU-4 Return Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-39f5-0d8b-39d2-f23c91a70cca . _:0b111ff8-39f5-0d8b-39d2-f23c91a70cca rdfs:label "" ; _:sourcePointName "RF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:fan, phIoT:his, phIoT:point, phIoT:return, phIoT:sensor, phScience:speed ; rdfs:label "Bravo RTU-4 Return Fan VFD Speed" ; ph:dis "Bravo RTU-4 Return Fan VFD Speed" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d8c-39d3-f23c91a70cca . _:0b111ff8-39f5-0d8c-39d3-f23c91a70cca rdfs:label "" ; _:sourcePointName "ACT_OUTPUT_SPEED" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-012b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Flow" ; ph:dis "Bravo RTU-4 Supply Air Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-39f5-0d8d-39d4-f23c91a70cca . _:0b111ff8-39f5-0d8d-39d4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SA CFM" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-012c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Humidity" ; ph:dis "Bravo RTU-4 Supply Air Humidity" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-39f5-0d8e-39d5-f23c91a70cca . _:0b111ff8-39f5-0d8e-39d5-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAH" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Humidity Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Humidity Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sp ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a41-58c0-39d6-f23c91a70cca . _:0b111ff8-3a41-58c0-39d6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Humidity SP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-012e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sp ; rdfs:label "Bravo RTU-4 Supply Air Pressure Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Pressure Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-3a41-58c1-39d7-f23c91a70cca . _:0b111ff8-3a41-58c1-39d7-f23c91a70cca rdfs:label "" ; _:sourcePointName "Static Stpt" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-012f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phScience:pressure, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Air Static Pressure" ; ph:dis "Bravo RTU-4 Supply Air Static Pressure" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "inH\u2082O" ; _:custom _:0b111ff8-3a41-58c2-39d8-f23c91a70cca . _:0b111ff8-3a41-58c2-39d8-f23c91a70cca rdfs:label "" ; _:sourcePointName "DISCH STATIC" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0130 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature" ; ph:dis "Bravo RTU-4 Supply Air Temperature" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a50-9b00-39d9-f23c91a70cca . _:0b111ff8-3a50-9b00-39d9-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0131 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sp, phScience:temp ; rdfs:label "Bravo RTU-4 Supply Air Temperature Setpoint" ; ph:dis "Bravo RTU-4 Supply Air Temperature Setpoint" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a50-9b01-39da-f23c91a70cca . _:0b111ff8-3a50-9b01-39da-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAT STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0132 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:fan, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo RTU-4 Supply Fan Status" ; ph:dis "Bravo RTU-4 Supply Fan Status" ; phIoT:equipRef _:b-0113 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3a50-9b02-39db-f23c91a70cca . _:0b111ff8-3a50-9b02-39db-f23c91a70cca rdfs:label "" ; _:sourcePointName "SF FAN STATUS" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0133 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo RTU-4 TU Air Flow (Auto-computed)" ; ph:dis "Bravo RTU-4 TU Air Flow (Auto-computed)" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a50-9b03-39dc-f23c91a70cca . _:0b111ff8-3a50-9b03-39dc-f23c91a70cca rdfs:label "" ; _:dataSyncDownSince "2020-03-12T01:00:04.793-04:00"^^xsd:dateTime ; _:dataSyncType "error" . _:b-0134 a phIoT:computed-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:computed, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo RTU-4 VAV Total Flow" ; ph:dis "Bravo RTU-4 VAV Total Flow" ; phIoT:equipRef _:b-0113 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-0135 ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a50-9b04-39dd-f23c91a70cca . _:0b111ff8-3a50-9b04-39dd-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime . _:b-0135 a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo RTUs" ; ph:dis "Bravo RTUs" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3a50-9b05-39de-f23c91a70cca . _:0b111ff8-3a50-9b05-39de-f23c91a70cca rdfs:label "" . _:b-0136 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler A" ; ph:dis "Bravo Steam Boiler A" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0b111ff8-3a50-9b06-39df-f23c91a70cca . _:0b111ff8-3a50-9b06-39df-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0137 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler A Boiler Status" ; ph:dis "Bravo Steam Boiler A Boiler Status" ; phIoT:equipRef _:b-0136 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0b111ff8-3a50-9b07-39e0-f23c91a70cca . _:0b111ff8-3a50-9b07-39e0-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrAsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0138 a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler B" ; ph:dis "Bravo Steam Boiler B" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0b111ff8-3a50-9b08-39e1-f23c91a70cca . _:0b111ff8-3a50-9b08-39e1-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-0139 a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler B Boiler Status" ; ph:dis "Bravo Steam Boiler B Boiler Status" ; phIoT:equipRef _:b-0138 ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0b111ff8-3a50-9b09-39e2-f23c91a70cca . _:0b111ff8-3a50-9b09-39e2-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrBsts" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-013a a phIoT:boiler ; ph:hasTag phIoT:boiler, phIoT:equip, phIoT:hvac ; rdfs:label "Bravo Steam Boiler C" ; ph:dis "Bravo Steam Boiler C" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; _:custom _:0b111ff8-3a50-9b0a-39e3-f23c91a70cca . _:0b111ff8-3a50-9b0a-39e3-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designMake "Lattner" ; _:designSteamPower 1350 ; _:designModel "WLF-40" . _:b-013b a phIoT:boiler, phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:boiler, phIoT:cur, phIoT:his, phIoT:point, phIoT:run, phIoT:sensor ; rdfs:label "Bravo Steam Boiler C Boiler Status" ; ph:dis "Bravo Steam Boiler C Boiler Status" ; phIoT:equipRef _:b-013a ; ph:kind "Bool" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-013c ; ph:tz "Chicago" ; _:custom _:0b111ff8-3a50-9b0b-39e4-f23c91a70cca . _:0b111ff8-3a50-9b0b-39e4-f23c91a70cca rdfs:label "" ; _:sourcePointName "StmBlrCsts" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-013c a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo Steam System" ; ph:dis "Bravo Steam System" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3a50-9b0c-39e5-f23c91a70cca . _:0b111ff8-3a50-9b0c-39e5-f23c91a70cca rdfs:label "" . _:b-013d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-1" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3a50-9b0d-39e6-f23c91a70cca . _:0b111ff8-3a50-9b0d-39e6-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-013e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-1 Damper Output" ; ph:dis "Bravo VAV 1-1 Damper Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a50-9b0e-39e7-f23c91a70cca . _:0b111ff8-3a50-9b0e-39e7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-013f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a50-9b0f-39e8-f23c91a70cca . _:0b111ff8-3a50-9b0f-39e8-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0140 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a50-9b10-39e9-f23c91a70cca . _:0b111ff8-3a50-9b10-39e9-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0141 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-1 Heating Valve Output" ; ph:dis "Bravo VAV 1-1 Heating Valve Output" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a5f-dd40-39ea-f23c91a70cca . _:0b111ff8-3a5f-dd40-39ea-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0142 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a5f-dd41-39eb-f23c91a70cca . _:0b111ff8-3a5f-dd41-39eb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0143 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-1 Zone Temperature" ; ph:dis "Bravo VAV 1-1 Zone Temperature" ; phIoT:equipRef _:b-013d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a5f-dd42-39ec-f23c91a70cca . _:0b111ff8-3a5f-dd42-39ec-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0144 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-10" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3a5f-dd43-39ed-f23c91a70cca . _:0b111ff8-3a5f-dd43-39ed-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-0145 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-10 Damper Output" ; ph:dis "Bravo VAV 1-10 Damper Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a5f-dd44-39ee-f23c91a70cca . _:0b111ff8-3a5f-dd44-39ee-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0146 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a5f-dd45-39ef-f23c91a70cca . _:0b111ff8-3a5f-dd45-39ef-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0147 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a5f-dd46-39f0-f23c91a70cca . _:0b111ff8-3a5f-dd46-39f0-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0148 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-10 Heating Valve Output" ; ph:dis "Bravo VAV 1-10 Heating Valve Output" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a5f-dd47-39f1-f23c91a70cca . _:0b111ff8-3a5f-dd47-39f1-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0149 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-10 Supply Air Temperature" ; ph:dis "Bravo VAV 1-10 Supply Air Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a5f-dd48-39f2-f23c91a70cca . _:0b111ff8-3a5f-dd48-39f2-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a5f-dd49-39f3-f23c91a70cca . _:0b111ff8-3a5f-dd49-39f3-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-014b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-10 Zone Temperature" ; ph:dis "Bravo VAV 1-10 Zone Temperature" ; phIoT:equipRef _:b-0144 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a8d-a400-39f4-f23c91a70cca . _:0b111ff8-3a8d-a400-39f4-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-014c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-11" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3a9c-e640-39f5-f23c91a70cca . _:0b111ff8-3a9c-e640-39f5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-014d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-11 Damper Output" ; ph:dis "Bravo VAV 1-11 Damper Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a9c-e641-39f6-f23c91a70cca . _:0b111ff8-3a9c-e641-39f6-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-014e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a9c-e642-39f7-f23c91a70cca . _:0b111ff8-3a9c-e642-39f7-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-014f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a9c-e643-39f8-f23c91a70cca . _:0b111ff8-3a9c-e643-39f8-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0150 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-11 Heating Valve Output" ; ph:dis "Bravo VAV 1-11 Heating Valve Output" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a9c-e644-39f9-f23c91a70cca . _:0b111ff8-3a9c-e644-39f9-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0151 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-11 Supply Air Temperature" ; ph:dis "Bravo VAV 1-11 Supply Air Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e645-39fa-f23c91a70cca . _:0b111ff8-3a9c-e645-39fa-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0152 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e646-39fb-f23c91a70cca . _:0b111ff8-3a9c-e646-39fb-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0153 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-11 Zone Temperature" ; ph:dis "Bravo VAV 1-11 Zone Temperature" ; phIoT:equipRef _:b-014c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e647-39fc-f23c91a70cca . _:0b111ff8-3a9c-e647-39fc-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0154 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-12" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3a9c-e648-39fd-f23c91a70cca . _:0b111ff8-3a9c-e648-39fd-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0155 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-12 Damper Output" ; ph:dis "Bravo VAV 1-12 Damper Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a9c-e649-39fe-f23c91a70cca . _:0b111ff8-3a9c-e649-39fe-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0156 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a9c-e64a-39ff-f23c91a70cca . _:0b111ff8-3a9c-e64a-39ff-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0157 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3a9c-e64b-3a00-f23c91a70cca . _:0b111ff8-3a9c-e64b-3a00-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0158 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-12 Heating Valve Output" ; ph:dis "Bravo VAV 1-12 Heating Valve Output" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a9c-e64c-3a01-f23c91a70cca . _:0b111ff8-3a9c-e64c-3a01-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0159 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-12 Supply Air Temperature" ; ph:dis "Bravo VAV 1-12 Supply Air Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e64d-3a02-f23c91a70cca . _:0b111ff8-3a9c-e64d-3a02-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-015a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e64e-3a03-f23c91a70cca . _:0b111ff8-3a9c-e64e-3a03-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-12 Zone Temperature" ; ph:dis "Bravo VAV 1-12 Zone Temperature" ; phIoT:equipRef _:b-0154 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3a9c-e64f-3a04-f23c91a70cca . _:0b111ff8-3a9c-e64f-3a04-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-015c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-13" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3a9c-e650-3a05-f23c91a70cca . _:0b111ff8-3a9c-e650-3a05-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 27 ; _:designHotWaterFlow 3 ; _:designAirFlow 1000 . _:b-015d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-13 Damper Output" ; ph:dis "Bravo VAV 1-13 Damper Output" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3a9c-e651-3a06-f23c91a70cca . _:0b111ff8-3a9c-e651-3a06-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-015e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3aac-2880-3a07-f23c91a70cca . _:0b111ff8-3aac-2880-3a07-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-015f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3aac-2881-3a08-f23c91a70cca . _:0b111ff8-3aac-2881-3a08-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0160 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-13 Heating Valve" ; ph:dis "Bravo VAV 1-13 Heating Valve" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3aac-2882-3a09-f23c91a70cca . _:0b111ff8-3aac-2882-3a09-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0161 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-13 Supply Air Temperature" ; ph:dis "Bravo VAV 1-13 Supply Air Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-2883-3a0a-f23c91a70cca . _:0b111ff8-3aac-2883-3a0a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0162 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-2884-3a0b-f23c91a70cca . _:0b111ff8-3aac-2884-3a0b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0163 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-13 Zone Temperature" ; ph:dis "Bravo VAV 1-13 Zone Temperature" ; phIoT:equipRef _:b-015c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-2885-3a0c-f23c91a70cca . _:0b111ff8-3aac-2885-3a0c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0164 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-14" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3aac-2886-3a0d-f23c91a70cca . _:0b111ff8-3aac-2886-3a0d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-0165 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-14 Damper Output" ; ph:dis "Bravo VAV 1-14 Damper Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3aac-2887-3a0e-f23c91a70cca . _:0b111ff8-3aac-2887-3a0e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0166 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3aac-2888-3a0f-f23c91a70cca . _:0b111ff8-3aac-2888-3a0f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0167 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3aac-2889-3a10-f23c91a70cca . _:0b111ff8-3aac-2889-3a10-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0168 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-14 Heating Valve Output" ; ph:dis "Bravo VAV 1-14 Heating Valve Output" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3aac-288a-3a11-f23c91a70cca . _:0b111ff8-3aac-288a-3a11-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0169 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-14 Supply Air Temperature" ; ph:dis "Bravo VAV 1-14 Supply Air Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-288b-3a12-f23c91a70cca . _:0b111ff8-3aac-288b-3a12-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-016a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-288c-3a13-f23c91a70cca . _:0b111ff8-3aac-288c-3a13-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-016b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-14 Zone Temperature" ; ph:dis "Bravo VAV 1-14 Zone Temperature" ; phIoT:equipRef _:b-0164 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aac-288d-3a14-f23c91a70cca . _:0b111ff8-3aac-288d-3a14-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-016c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-15" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3aac-288e-3a15-f23c91a70cca . _:0b111ff8-3aac-288e-3a15-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-016d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-15 Damper Output" ; ph:dis "Bravo VAV 1-15 Damper Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3abb-6ac0-3a16-f23c91a70cca . _:0b111ff8-3abb-6ac0-3a16-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-016e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6ac1-3a17-f23c91a70cca . _:0b111ff8-3abb-6ac1-3a17-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-016f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6ac2-3a18-f23c91a70cca . _:0b111ff8-3abb-6ac2-3a18-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0170 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-15 Heating Valve Output" ; ph:dis "Bravo VAV 1-15 Heating Valve Output" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3abb-6ac3-3a19-f23c91a70cca . _:0b111ff8-3abb-6ac3-3a19-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0171 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-15 Supply Air Temperature" ; ph:dis "Bravo VAV 1-15 Supply Air Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6ac4-3a1a-f23c91a70cca . _:0b111ff8-3abb-6ac4-3a1a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0172 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6ac5-3a1b-f23c91a70cca . _:0b111ff8-3abb-6ac5-3a1b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0173 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-15 Zone Temperature" ; ph:dis "Bravo VAV 1-15 Zone Temperature" ; phIoT:equipRef _:b-016c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6ac6-3a1c-f23c91a70cca . _:0b111ff8-3abb-6ac6-3a1c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0174 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-16" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3abb-6ac7-3a1d-f23c91a70cca . _:0b111ff8-3abb-6ac7-3a1d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0175 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-16 Damper Output" ; ph:dis "Bravo VAV 1-16 Damper Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3abb-6ac8-3a1e-f23c91a70cca . _:0b111ff8-3abb-6ac8-3a1e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0176 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6ac9-3a1f-f23c91a70cca . _:0b111ff8-3abb-6ac9-3a1f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0177 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6aca-3a20-f23c91a70cca . _:0b111ff8-3abb-6aca-3a20-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0178 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-16 Heating Valve Output" ; ph:dis "Bravo VAV 1-16 Heating Valve Output" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3abb-6acb-3a21-f23c91a70cca . _:0b111ff8-3abb-6acb-3a21-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0179 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-16 Supply Air Temperature" ; ph:dis "Bravo VAV 1-16 Supply Air Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6acc-3a22-f23c91a70cca . _:0b111ff8-3abb-6acc-3a22-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6acd-3a23-f23c91a70cca . _:0b111ff8-3abb-6acd-3a23-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-017b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-16 Zone Temperature" ; ph:dis "Bravo VAV 1-16 Zone Temperature" ; phIoT:equipRef _:b-0174 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3abb-6ace-3a24-f23c91a70cca . _:0b111ff8-3abb-6ace-3a24-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-017c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-17" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3abb-6acf-3a25-f23c91a70cca . _:0b111ff8-3abb-6acf-3a25-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-017d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-17 Damper Output" ; ph:dis "Bravo VAV 1-17 Damper Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3abb-6ad0-3a26-f23c91a70cca . _:0b111ff8-3abb-6ad0-3a26-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6ad1-3a27-f23c91a70cca . _:0b111ff8-3abb-6ad1-3a27-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-017f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3abb-6ad2-3a28-f23c91a70cca . _:0b111ff8-3abb-6ad2-3a28-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0180 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-17 Heating Valve Output" ; ph:dis "Bravo VAV 1-17 Heating Valve Output" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3aca-ad00-3a29-f23c91a70cca . _:0b111ff8-3aca-ad00-3a29-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0181 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-17 Supply Air Temperature" ; ph:dis "Bravo VAV 1-17 Supply Air Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aca-ad01-3a2a-f23c91a70cca . _:0b111ff8-3aca-ad01-3a2a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0182 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3aca-ad02-3a2b-f23c91a70cca . _:0b111ff8-3aca-ad02-3a2b-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0183 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-17 Zone Temperature" ; ph:dis "Bravo VAV 1-17 Zone Temperature" ; phIoT:equipRef _:b-017c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3af8-73c0-3a2c-f23c91a70cca . _:0b111ff8-3af8-73c0-3a2c-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0184 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-18" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3af8-73c1-3a2d-f23c91a70cca . _:0b111ff8-3af8-73c1-3a2d-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0185 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-18 Damper Output" ; ph:dis "Bravo VAV 1-18 Damper Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3af8-73c2-3a2e-f23c91a70cca . _:0b111ff8-3af8-73c2-3a2e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0186 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3af8-73c3-3a2f-f23c91a70cca . _:0b111ff8-3af8-73c3-3a2f-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0187 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3af8-73c4-3a30-f23c91a70cca . _:0b111ff8-3af8-73c4-3a30-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0188 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-18 Heating Valve Output" ; ph:dis "Bravo VAV 1-18 Heating Valve Output" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3af8-73c5-3a31-f23c91a70cca . _:0b111ff8-3af8-73c5-3a31-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0189 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-18 Supply Air Temperature" ; ph:dis "Bravo VAV 1-18 Supply Air Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3af8-73c6-3a32-f23c91a70cca . _:0b111ff8-3af8-73c6-3a32-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-018a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b07-b600-3a33-f23c91a70cca . _:0b111ff8-3b07-b600-3a33-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-018b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-18 Zone Temperature" ; ph:dis "Bravo VAV 1-18 Zone Temperature" ; phIoT:equipRef _:b-0184 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b07-b601-3a34-f23c91a70cca . _:0b111ff8-3b07-b601-3a34-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-018c a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-19" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b07-b602-3a35-f23c91a70cca . _:0b111ff8-3b07-b602-3a35-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 30.9 ; _:designHotWaterFlow 1.45 ; _:designAirFlow 2400 . _:b-018d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-19 Damper Output" ; ph:dis "Bravo VAV 1-19 Damper Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b07-b603-3a36-f23c91a70cca . _:0b111ff8-3b07-b603-3a36-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b07-b604-3a37-f23c91a70cca . _:0b111ff8-3b07-b604-3a37-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-018f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b07-b605-3a38-f23c91a70cca . _:0b111ff8-3b07-b605-3a38-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0190 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-19 Heating Valve Output" ; ph:dis "Bravo VAV 1-19 Heating Valve Output" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b07-b606-3a39-f23c91a70cca . _:0b111ff8-3b07-b606-3a39-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0191 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-19 Supply Air Temperature" ; ph:dis "Bravo VAV 1-19 Supply Air Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b07-b607-3a3a-f23c91a70cca . _:0b111ff8-3b07-b607-3a3a-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0192 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Humidity" ; ph:dis "Bravo VAV 1-19 Zone Air Humidity" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b07-b608-3a3b-f23c91a70cca . _:0b111ff8-3b07-b608-3a3b-f23c91a70cca rdfs:label "" ; _:predictionConf 0.6984488664169048 ; _:sourcePointName "Humidity" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0193 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b07-b609-3a3c-f23c91a70cca . _:0b111ff8-3b07-b609-3a3c-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0194 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-19 Zone Temperature" ; ph:dis "Bravo VAV 1-19 Zone Temperature" ; phIoT:equipRef _:b-018c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b07-b60a-3a3d-f23c91a70cca . _:0b111ff8-3b07-b60a-3a3d-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0195 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-2" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b07-b60b-3a3e-f23c91a70cca . _:0b111ff8-3b07-b60b-3a3e-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.5 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-0196 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-2 Damper Output" ; ph:dis "Bravo VAV 1-2 Damper Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b07-b60c-3a3f-f23c91a70cca . _:0b111ff8-3b07-b60c-3a3f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0197 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b07-b60d-3a40-f23c91a70cca . _:0b111ff8-3b07-b60d-3a40-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0198 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b07-b60e-3a41-f23c91a70cca . _:0b111ff8-3b07-b60e-3a41-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0199 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-2 Heating Valve Output" ; ph:dis "Bravo VAV 1-2 Heating Valve Output" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b16-f840-3a42-f23c91a70cca . _:0b111ff8-3b16-f840-3a42-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-2 Supply Air Temperature" ; ph:dis "Bravo VAV 1-2 Supply Air Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f841-3a43-f23c91a70cca . _:0b111ff8-3b16-f841-3a43-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-019b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f842-3a44-f23c91a70cca . _:0b111ff8-3b16-f842-3a44-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-019c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-2 Zone Temperature" ; ph:dis "Bravo VAV 1-2 Zone Temperature" ; phIoT:equipRef _:b-0195 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f843-3a45-f23c91a70cca . _:0b111ff8-3b16-f843-3a45-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-019d a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-20" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b16-f844-3a46-f23c91a70cca . _:0b111ff8-3b16-f844-3a46-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 0.28 ; _:designAirFlow 800 . _:b-019e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-20 Damper Output" ; ph:dis "Bravo VAV 1-20 Damper Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b16-f845-3a47-f23c91a70cca . _:0b111ff8-3b16-f845-3a47-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-019f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b16-f846-3a48-f23c91a70cca . _:0b111ff8-3b16-f846-3a48-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b16-f847-3a49-f23c91a70cca . _:0b111ff8-3b16-f847-3a49-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01a1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-20 Heating Valve Output" ; ph:dis "Bravo VAV 1-20 Heating Valve Output" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b16-f848-3a4a-f23c91a70cca . _:0b111ff8-3b16-f848-3a4a-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-20 Supply Air Temperature" ; ph:dis "Bravo VAV 1-20 Supply Air Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f849-3a4b-f23c91a70cca . _:0b111ff8-3b16-f849-3a4b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f84a-3a4c-f23c91a70cca . _:0b111ff8-3b16-f84a-3a4c-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-20 Zone Temperature" ; ph:dis "Bravo VAV 1-20 Zone Temperature" ; phIoT:equipRef _:b-019d ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b16-f84b-3a4d-f23c91a70cca . _:0b111ff8-3b16-f84b-3a4d-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01a5 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-3" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b16-f84c-3a4e-f23c91a70cca . _:0b111ff8-3b16-f84c-3a4e-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-3 Damper Output" ; ph:dis "Bravo VAV 1-3 Damper Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b16-f84d-3a4f-f23c91a70cca . _:0b111ff8-3b16-f84d-3a4f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b26-3a80-3a50-f23c91a70cca . _:0b111ff8-3b26-3a80-3a50-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b26-3a81-3a51-f23c91a70cca . _:0b111ff8-3b26-3a81-3a51-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01a9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-3 Heating Valve Output" ; ph:dis "Bravo VAV 1-3 Heating Valve Output" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b26-3a82-3a52-f23c91a70cca . _:0b111ff8-3b26-3a82-3a52-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-3 Supply Air Humidity" ; ph:dis "Bravo VAV 1-3 Supply Air Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b26-3a83-3a53-f23c91a70cca . _:0b111ff8-3b26-3a83-3a53-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-3 Supply Air Temperature" ; ph:dis "Bravo VAV 1-3 Supply Air Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b26-3a84-3a54-f23c91a70cca . _:0b111ff8-3b26-3a84-3a54-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b26-3a85-3a55-f23c91a70cca . _:0b111ff8-3b26-3a85-3a55-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-3 Zone Relative Humidity" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b26-3a86-3a56-f23c91a70cca . _:0b111ff8-3b26-3a86-3a56-f23c91a70cca rdfs:label "" ; _:predictionConf 0.7237593125289187 ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-3 Zone Temperature" ; ph:dis "Bravo VAV 1-3 Zone Temperature" ; phIoT:equipRef _:b-01a5 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b26-3a87-3a57-f23c91a70cca . _:0b111ff8-3b26-3a87-3a57-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01af a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-4" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b26-3a88-3a58-f23c91a70cca . _:0b111ff8-3b26-3a88-3a58-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 3.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-4 Damper Output" ; ph:dis "Bravo VAV 1-4 Damper Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b26-3a89-3a59-f23c91a70cca . _:0b111ff8-3b26-3a89-3a59-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01b1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b26-3a8a-3a5a-f23c91a70cca . _:0b111ff8-3b26-3a8a-3a5a-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b26-3a8b-3a5b-f23c91a70cca . _:0b111ff8-3b26-3a8b-3a5b-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-4 Heating Valve Output" ; ph:dis "Bravo VAV 1-4 Heating Valve Output" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b26-3a8c-3a5c-f23c91a70cca . _:0b111ff8-3b26-3a8c-3a5c-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-4 Supply Air Temperature" ; ph:dis "Bravo VAV 1-4 Supply Air Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b26-3a8d-3a5d-f23c91a70cca . _:0b111ff8-3b26-3a8d-3a5d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b26-3a8e-3a5e-f23c91a70cca . _:0b111ff8-3b26-3a8e-3a5e-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-4 Zone Temperature" ; ph:dis "Bravo VAV 1-4 Zone Temperature" ; phIoT:equipRef _:b-01af ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b63-4380-3a5f-f23c91a70cca . _:0b111ff8-3b63-4380-3a5f-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01b7 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-5" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b63-4381-3a60-f23c91a70cca . _:0b111ff8-3b63-4381-3a60-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 450 . _:b-01b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-5 Damper Output" ; ph:dis "Bravo VAV 1-5 Damper Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b63-4382-3a61-f23c91a70cca . _:0b111ff8-3b63-4382-3a61-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01b9 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b63-4383-3a62-f23c91a70cca . _:0b111ff8-3b63-4383-3a62-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b63-4384-3a63-f23c91a70cca . _:0b111ff8-3b63-4384-3a63-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-5 Heating Valve Output" ; ph:dis "Bravo VAV 1-5 Heating Valve Output" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b63-4385-3a64-f23c91a70cca . _:0b111ff8-3b63-4385-3a64-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-5 Supply Air Temperature" ; ph:dis "Bravo VAV 1-5 Supply Air Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b63-4386-3a65-f23c91a70cca . _:0b111ff8-3b63-4386-3a65-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b63-4387-3a66-f23c91a70cca . _:0b111ff8-3b63-4387-3a66-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-5 Zone Temperature" ; ph:dis "Bravo VAV 1-5 Zone Temperature" ; phIoT:equipRef _:b-01b7 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b63-4388-3a67-f23c91a70cca . _:0b111ff8-3b63-4388-3a67-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01bf a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-6" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b63-4389-3a68-f23c91a70cca . _:0b111ff8-3b63-4389-3a68-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 83.5 ; _:designHotWaterFlow 12 ; _:designAirFlow 3000 . _:b-01c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-6 Damper Output" ; ph:dis "Bravo VAV 1-6 Damper Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85c0-3a69-f23c91a70cca . _:0b111ff8-3b72-85c0-3a69-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01c1 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b72-85c1-3a6a-f23c91a70cca . _:0b111ff8-3b72-85c1-3a6a-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b72-85c2-3a6b-f23c91a70cca . _:0b111ff8-3b72-85c2-3a6b-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-6 Heating Valve Output" ; ph:dis "Bravo VAV 1-6 Heating Valve Output" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85c3-3a6c-f23c91a70cca . _:0b111ff8-3b72-85c3-3a6c-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-6 Supply Air Humidity" ; ph:dis "Bravo VAV 1-6 Supply Air Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85c4-3a6d-f23c91a70cca . _:0b111ff8-3b72-85c4-3a6d-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisChgrHumid" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-6 Supply Air Temperature" ; ph:dis "Bravo VAV 1-6 Supply Air Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b72-85c5-3a6e-f23c91a70cca . _:0b111ff8-3b72-85c5-3a6e-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b72-85c6-3a6f-f23c91a70cca . _:0b111ff8-3b72-85c6-3a6f-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-01c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Relative Humidity" ; ph:dis "Bravo VAV 1-6 Zone Relative Humidity" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:pointFunction phIoT:sensor ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85c7-3a70-f23c91a70cca . _:0b111ff8-3b72-85c7-3a70-f23c91a70cca rdfs:label "" ; _:sourcePointName "SpaceHum" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-01c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-6 Zone Temperature" ; ph:dis "Bravo VAV 1-6 Zone Temperature" ; phIoT:equipRef _:b-01bf ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b72-85c8-3a71-f23c91a70cca . _:0b111ff8-3b72-85c8-3a71-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-7" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b72-85c9-3a72-f23c91a70cca . _:0b111ff8-3b72-85c9-3a72-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 450 . _:b-01ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-7 Damper Output" ; ph:dis "Bravo VAV 1-7 Damper Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85ca-3a73-f23c91a70cca . _:0b111ff8-3b72-85ca-3a73-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b72-85cb-3a74-f23c91a70cca . _:0b111ff8-3b72-85cb-3a74-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b72-85cc-3a75-f23c91a70cca . _:0b111ff8-3b72-85cc-3a75-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-7 Heating Valve Output" ; ph:dis "Bravo VAV 1-7 Heating Valve Output" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b72-85cd-3a76-f23c91a70cca . _:0b111ff8-3b72-85cd-3a76-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-7 Supply Air Temperature" ; ph:dis "Bravo VAV 1-7 Supply Air Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c800-3a77-f23c91a70cca . _:0b111ff8-3b81-c800-3a77-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c801-3a78-f23c91a70cca . _:0b111ff8-3b81-c801-3a78-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-7 Zone Temperature" ; ph:dis "Bravo VAV 1-7 Zone Temperature" ; phIoT:equipRef _:b-01c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c802-3a79-f23c91a70cca . _:0b111ff8-3b81-c802-3a79-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-8" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b81-c803-3a7a-f23c91a70cca . _:0b111ff8-3b81-c803-3a7a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.8 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-01d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-8 Damper Output" ; ph:dis "Bravo VAV 1-8 Damper Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b81-c804-3a7b-f23c91a70cca . _:0b111ff8-3b81-c804-3a7b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b81-c805-3a7c-f23c91a70cca . _:0b111ff8-3b81-c805-3a7c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b81-c806-3a7d-f23c91a70cca . _:0b111ff8-3b81-c806-3a7d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-8 Heating Valve Output" ; ph:dis "Bravo VAV 1-8 Heating Valve Output" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b81-c807-3a7e-f23c91a70cca . _:0b111ff8-3b81-c807-3a7e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-8 Supply Air Temperature" ; ph:dis "Bravo VAV 1-8 Supply Air Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c808-3a7f-f23c91a70cca . _:0b111ff8-3b81-c808-3a7f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c809-3a80-f23c91a70cca . _:0b111ff8-3b81-c809-3a80-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-8 Zone Temperature" ; ph:dis "Bravo VAV 1-8 Zone Temperature" ; phIoT:equipRef _:b-01d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c80a-3a81-f23c91a70cca . _:0b111ff8-3b81-c80a-3a81-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 1-9" ; phIoT:airRef _:b-00ac ; ph:dis "Bravo VAV 1-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b81-c80b-3a82-f23c91a70cca . _:0b111ff8-3b81-c80b-3a82-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 15.3 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 875 . _:b-01da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 1-9 Damper Output" ; ph:dis "Bravo VAV 1-9 Damper Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b81-c80c-3a83-f23c91a70cca . _:0b111ff8-3b81-c80c-3a83-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b81-c80d-3a84-f23c91a70cca . _:0b111ff8-3b81-c80d-3a84-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 1-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b81-c80e-3a85-f23c91a70cca . _:0b111ff8-3b81-c80e-3a85-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 1-9 Heating Valve Output" ; ph:dis "Bravo VAV 1-9 Heating Valve Output" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b81-c80f-3a86-f23c91a70cca . _:0b111ff8-3b81-c80f-3a86-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-01de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 1-9 Supply Air Temperature" ; ph:dis "Bravo VAV 1-9 Supply Air Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c810-3a87-f23c91a70cca . _:0b111ff8-3b81-c810-3a87-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 1-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b81-c811-3a88-f23c91a70cca . _:0b111ff8-3b81-c811-3a88-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 1-9 Zone Temperature" ; ph:dis "Bravo VAV 1-9 Zone Temperature" ; phIoT:equipRef _:b-01d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b91-0a40-3a89-f23c91a70cca . _:0b111ff8-3b91-0a40-3a89-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-1" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3b91-0a41-3a8a-f23c91a70cca . _:0b111ff8-3b91-0a41-3a8a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-1 Damper Output" ; ph:dis "Bravo VAV 2-1 Damper Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b91-0a42-3a8b-f23c91a70cca . _:0b111ff8-3b91-0a42-3a8b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b91-0a43-3a8c-f23c91a70cca . _:0b111ff8-3b91-0a43-3a8c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3b91-0a44-3a8d-f23c91a70cca . _:0b111ff8-3b91-0a44-3a8d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-1 Heating Valve Output" ; ph:dis "Bravo VAV 2-1 Heating Valve Output" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3b91-0a45-3a8e-f23c91a70cca . _:0b111ff8-3b91-0a45-3a8e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-1 Supply Air Temperature" ; ph:dis "Bravo VAV 2-1 Supply Air Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3b91-0a46-3a8f-f23c91a70cca . _:0b111ff8-3b91-0a46-3a8f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bbe-d100-3a90-f23c91a70cca . _:0b111ff8-3bbe-d100-3a90-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-1 Zone Temperature" ; ph:dis "Bravo VAV 2-1 Zone Temperature" ; phIoT:equipRef _:b-01e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bbe-d101-3a91-f23c91a70cca . _:0b111ff8-3bbe-d101-3a91-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-10" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bce-1340-3a92-f23c91a70cca . _:0b111ff8-3bce-1340-3a92-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 4.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 175 . _:b-01ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-10 Damper Output" ; ph:dis "Bravo VAV 2-10 Damper Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bce-1341-3a93-f23c91a70cca . _:0b111ff8-3bce-1341-3a93-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bce-1342-3a94-f23c91a70cca . _:0b111ff8-3bce-1342-3a94-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-01ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bce-1343-3a95-f23c91a70cca . _:0b111ff8-3bce-1343-3a95-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-01ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-10 Heating Valve Output" ; ph:dis "Bravo VAV 2-10 Heating Valve Output" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bce-1344-3a96-f23c91a70cca . _:0b111ff8-3bce-1344-3a96-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-10 Supply Air Temperature" ; ph:dis "Bravo VAV 2-10 Supply Air Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-1345-3a97-f23c91a70cca . _:0b111ff8-3bce-1345-3a97-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-01ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-1346-3a98-f23c91a70cca . _:0b111ff8-3bce-1346-3a98-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-01f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-10 Zone Temperature" ; ph:dis "Bravo VAV 2-10 Zone Temperature" ; phIoT:equipRef _:b-01e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-1347-3a99-f23c91a70cca . _:0b111ff8-3bce-1347-3a99-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-01f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-11" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bce-1348-3a9a-f23c91a70cca . _:0b111ff8-3bce-1348-3a9a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-01f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-11 Damper Output" ; ph:dis "Bravo VAV 2-11 Damper Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bce-1349-3a9b-f23c91a70cca . _:0b111ff8-3bce-1349-3a9b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bce-134a-3a9c-f23c91a70cca . _:0b111ff8-3bce-134a-3a9c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-01f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bce-134b-3a9d-f23c91a70cca . _:0b111ff8-3bce-134b-3a9d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-01f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-11 Heating Valve Output" ; ph:dis "Bravo VAV 2-11 Heating Valve Output" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bce-134c-3a9e-f23c91a70cca . _:0b111ff8-3bce-134c-3a9e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-01f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-11 Supply Air Temperature" ; ph:dis "Bravo VAV 2-11 Supply Air Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-134d-3a9f-f23c91a70cca . _:0b111ff8-3bce-134d-3a9f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-01f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-134e-3aa0-f23c91a70cca . _:0b111ff8-3bce-134e-3aa0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-11 Zone Temperature" ; ph:dis "Bravo VAV 2-11 Zone Temperature" ; phIoT:equipRef _:b-01f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bce-134f-3aa1-f23c91a70cca . _:0b111ff8-3bce-134f-3aa1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-01f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-12" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bce-1350-3aa2-f23c91a70cca . _:0b111ff8-3bce-1350-3aa2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 4.6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-01fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-12 Damper Output" ; ph:dis "Bravo VAV 2-12 Damper Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bdd-5580-3aa3-f23c91a70cca . _:0b111ff8-3bdd-5580-3aa3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-01fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bdd-5581-3aa4-f23c91a70cca . _:0b111ff8-3bdd-5581-3aa4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bdd-5582-3aa5-f23c91a70cca . _:0b111ff8-3bdd-5582-3aa5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-01fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-12 Heating Valve Output" ; ph:dis "Bravo VAV 2-12 Heating Valve Output" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bdd-5583-3aa6-f23c91a70cca . _:0b111ff8-3bdd-5583-3aa6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-01fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-12 Supply Air Temperature" ; ph:dis "Bravo VAV 2-12 Supply Air Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-5584-3aa7-f23c91a70cca . _:0b111ff8-3bdd-5584-3aa7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-01ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-5585-3aa8-f23c91a70cca . _:0b111ff8-3bdd-5585-3aa8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0200 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-12 Zone Temperature" ; ph:dis "Bravo VAV 2-12 Zone Temperature" ; phIoT:equipRef _:b-01f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-5586-3aa9-f23c91a70cca . _:0b111ff8-3bdd-5586-3aa9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0201 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-13" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bdd-5587-3aaa-f23c91a70cca . _:0b111ff8-3bdd-5587-3aaa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0202 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-13 Damper Output" ; ph:dis "Bravo VAV 2-13 Damper Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bdd-5588-3aab-f23c91a70cca . _:0b111ff8-3bdd-5588-3aab-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0203 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bdd-5589-3aac-f23c91a70cca . _:0b111ff8-3bdd-5589-3aac-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0204 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bdd-558a-3aad-f23c91a70cca . _:0b111ff8-3bdd-558a-3aad-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0205 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-13 Heating Valve Output" ; ph:dis "Bravo VAV 2-13 Heating Valve Output" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bdd-558b-3aae-f23c91a70cca . _:0b111ff8-3bdd-558b-3aae-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0206 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-13 Supply Air Temperature" ; ph:dis "Bravo VAV 2-13 Supply Air Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-558c-3aaf-f23c91a70cca . _:0b111ff8-3bdd-558c-3aaf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0207 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-558d-3ab0-f23c91a70cca . _:0b111ff8-3bdd-558d-3ab0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0208 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-13 Zone Temperature" ; ph:dis "Bravo VAV 2-13 Zone Temperature" ; phIoT:equipRef _:b-0201 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bdd-558e-3ab1-f23c91a70cca . _:0b111ff8-3bdd-558e-3ab1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0209 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-14" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bdd-558f-3ab2-f23c91a70cca . _:0b111ff8-3bdd-558f-3ab2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 24.2 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1450 . _:b-020a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-14 Damper Output" ; ph:dis "Bravo VAV 2-14 Damper Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bdd-5590-3ab3-f23c91a70cca . _:0b111ff8-3bdd-5590-3ab3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-020b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bdd-5591-3ab4-f23c91a70cca . _:0b111ff8-3bdd-5591-3ab4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-020c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bec-97c0-3ab5-f23c91a70cca . _:0b111ff8-3bec-97c0-3ab5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-020d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-14 Heating Valve Output" ; ph:dis "Bravo VAV 2-14 Heating Valve Output" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bec-97c1-3ab6-f23c91a70cca . _:0b111ff8-3bec-97c1-3ab6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-020e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-14 Supply Air Temperature" ; ph:dis "Bravo VAV 2-14 Supply Air Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97c2-3ab7-f23c91a70cca . _:0b111ff8-3bec-97c2-3ab7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-020f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97c3-3ab8-f23c91a70cca . _:0b111ff8-3bec-97c3-3ab8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0210 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-14 Zone Temperature" ; ph:dis "Bravo VAV 2-14 Zone Temperature" ; phIoT:equipRef _:b-0209 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97c4-3ab9-f23c91a70cca . _:0b111ff8-3bec-97c4-3ab9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0211 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-15" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bec-97c5-3aba-f23c91a70cca . _:0b111ff8-3bec-97c5-3aba-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.7 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0212 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-15 Damper Output" ; ph:dis "Bravo VAV 2-15 Damper Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bec-97c6-3abb-f23c91a70cca . _:0b111ff8-3bec-97c6-3abb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0213 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bec-97c7-3abc-f23c91a70cca . _:0b111ff8-3bec-97c7-3abc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0214 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bec-97c8-3abd-f23c91a70cca . _:0b111ff8-3bec-97c8-3abd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0215 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-15 Heating Valve Output" ; ph:dis "Bravo VAV 2-15 Heating Valve Output" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bec-97c9-3abe-f23c91a70cca . _:0b111ff8-3bec-97c9-3abe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0216 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-15 Supply Air Temperature" ; ph:dis "Bravo VAV 2-15 Supply Air Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97ca-3abf-f23c91a70cca . _:0b111ff8-3bec-97ca-3abf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0217 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97cb-3ac0-f23c91a70cca . _:0b111ff8-3bec-97cb-3ac0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0218 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-15 Zone Temperature" ; ph:dis "Bravo VAV 2-15 Zone Temperature" ; phIoT:equipRef _:b-0211 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97cc-3ac1-f23c91a70cca . _:0b111ff8-3bec-97cc-3ac1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0219 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-16" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bec-97cd-3ac2-f23c91a70cca . _:0b111ff8-3bec-97cd-3ac2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-021a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-16 Damper Output" ; ph:dis "Bravo VAV 2-16 Damper Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bec-97ce-3ac3-f23c91a70cca . _:0b111ff8-3bec-97ce-3ac3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-021b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bec-97cf-3ac4-f23c91a70cca . _:0b111ff8-3bec-97cf-3ac4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-021c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3bec-97d0-3ac5-f23c91a70cca . _:0b111ff8-3bec-97d0-3ac5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-021d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-16 Heating Valve Output" ; ph:dis "Bravo VAV 2-16 Heating Valve Output" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3bec-97d1-3ac6-f23c91a70cca . _:0b111ff8-3bec-97d1-3ac6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-021e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-16 Supply Air Temperature" ; ph:dis "Bravo VAV 2-16 Supply Air Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bec-97d2-3ac7-f23c91a70cca . _:0b111ff8-3bec-97d2-3ac7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-021f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bfb-da00-3ac8-f23c91a70cca . _:0b111ff8-3bfb-da00-3ac8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0220 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-16 Zone Temperature" ; ph:dis "Bravo VAV 2-16 Zone Temperature" ; phIoT:equipRef _:b-0219 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3bfb-da01-3ac9-f23c91a70cca . _:0b111ff8-3bfb-da01-3ac9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0221 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-17" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3bfb-da02-3aca-f23c91a70cca . _:0b111ff8-3bfb-da02-3aca-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 400 . _:b-0222 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-17 Damper Output" ; ph:dis "Bravo VAV 2-17 Damper Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c29-a0c0-3acb-f23c91a70cca . _:0b111ff8-3c29-a0c0-3acb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0223 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c29-a0c1-3acc-f23c91a70cca . _:0b111ff8-3c29-a0c1-3acc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0224 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c29-a0c2-3acd-f23c91a70cca . _:0b111ff8-3c29-a0c2-3acd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0225 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-17 Heating Valve Output" ; ph:dis "Bravo VAV 2-17 Heating Valve Output" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c29-a0c3-3ace-f23c91a70cca . _:0b111ff8-3c29-a0c3-3ace-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0226 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-17 Supply Air Temperature" ; ph:dis "Bravo VAV 2-17 Supply Air Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c29-a0c4-3acf-f23c91a70cca . _:0b111ff8-3c29-a0c4-3acf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0227 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c29-a0c5-3ad0-f23c91a70cca . _:0b111ff8-3c29-a0c5-3ad0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0228 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-17 Zone Temperature" ; ph:dis "Bravo VAV 2-17 Zone Temperature" ; phIoT:equipRef _:b-0221 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c29-a0c6-3ad1-f23c91a70cca . _:0b111ff8-3c29-a0c6-3ad1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0229 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-18" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c29-a0c7-3ad2-f23c91a70cca . _:0b111ff8-3c29-a0c7-3ad2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 15 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 550 . _:b-022a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-18 Damper Output" ; ph:dis "Bravo VAV 2-18 Damper Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c38-e300-3ad3-f23c91a70cca . _:0b111ff8-3c38-e300-3ad3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c38-e301-3ad4-f23c91a70cca . _:0b111ff8-3c38-e301-3ad4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-022c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c38-e302-3ad5-f23c91a70cca . _:0b111ff8-3c38-e302-3ad5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-022d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-18 Heating Valve Output" ; ph:dis "Bravo VAV 2-18 Heating Valve Output" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c38-e303-3ad6-f23c91a70cca . _:0b111ff8-3c38-e303-3ad6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-022e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-18 Supply Air Temperature" ; ph:dis "Bravo VAV 2-18 Supply Air Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e304-3ad7-f23c91a70cca . _:0b111ff8-3c38-e304-3ad7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-022f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e305-3ad8-f23c91a70cca . _:0b111ff8-3c38-e305-3ad8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0230 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-18 Zone Temperature" ; ph:dis "Bravo VAV 2-18 Zone Temperature" ; phIoT:equipRef _:b-0229 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e306-3ad9-f23c91a70cca . _:0b111ff8-3c38-e306-3ad9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0231 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-19" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c38-e307-3ada-f23c91a70cca . _:0b111ff8-3c38-e307-3ada-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0232 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-19 Damper Output" ; ph:dis "Bravo VAV 2-19 Damper Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c38-e308-3adb-f23c91a70cca . _:0b111ff8-3c38-e308-3adb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0233 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c38-e309-3adc-f23c91a70cca . _:0b111ff8-3c38-e309-3adc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0234 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c38-e30a-3add-f23c91a70cca . _:0b111ff8-3c38-e30a-3add-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0235 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-19 Heating Valve Output" ; ph:dis "Bravo VAV 2-19 Heating Valve Output" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c38-e30b-3ade-f23c91a70cca . _:0b111ff8-3c38-e30b-3ade-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0236 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-19 Supply Air Temperature" ; ph:dis "Bravo VAV 2-19 Supply Air Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e30c-3adf-f23c91a70cca . _:0b111ff8-3c38-e30c-3adf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0237 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e30d-3ae0-f23c91a70cca . _:0b111ff8-3c38-e30d-3ae0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0238 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-19 Zone Temperature" ; ph:dis "Bravo VAV 2-19 Zone Temperature" ; phIoT:equipRef _:b-0231 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c38-e30e-3ae1-f23c91a70cca . _:0b111ff8-3c38-e30e-3ae1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0239 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-2" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c38-e30f-3ae2-f23c91a70cca . _:0b111ff8-3c38-e30f-3ae2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-023a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-2 Damper Output" ; ph:dis "Bravo VAV 2-2 Damper Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c38-e310-3ae3-f23c91a70cca . _:0b111ff8-3c38-e310-3ae3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-023b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2540-3ae4-f23c91a70cca . _:0b111ff8-3c48-2540-3ae4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-023c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2541-3ae5-f23c91a70cca . _:0b111ff8-3c48-2541-3ae5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-023d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-2 Heating Valve Output" ; ph:dis "Bravo VAV 2-2 Heating Valve Output" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c48-2542-3ae6-f23c91a70cca . _:0b111ff8-3c48-2542-3ae6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-023e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-2 Supply Air Temperature" ; ph:dis "Bravo VAV 2-2 Supply Air Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-2543-3ae7-f23c91a70cca . _:0b111ff8-3c48-2543-3ae7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-023f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-2544-3ae8-f23c91a70cca . _:0b111ff8-3c48-2544-3ae8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0240 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-2 Zone Temperature" ; ph:dis "Bravo VAV 2-2 Zone Temperature" ; phIoT:equipRef _:b-0239 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-2545-3ae9-f23c91a70cca . _:0b111ff8-3c48-2545-3ae9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0241 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-20" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c48-2546-3aea-f23c91a70cca . _:0b111ff8-3c48-2546-3aea-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-0242 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-20 Damper Output" ; ph:dis "Bravo VAV 2-20 Damper Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c48-2547-3aeb-f23c91a70cca . _:0b111ff8-3c48-2547-3aeb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0243 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2548-3aec-f23c91a70cca . _:0b111ff8-3c48-2548-3aec-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0244 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2549-3aed-f23c91a70cca . _:0b111ff8-3c48-2549-3aed-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0245 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-20 Heating Valve Output" ; ph:dis "Bravo VAV 2-20 Heating Valve Output" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c48-254a-3aee-f23c91a70cca . _:0b111ff8-3c48-254a-3aee-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0246 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-20 Supply Air Temperature" ; ph:dis "Bravo VAV 2-20 Supply Air Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-254b-3aef-f23c91a70cca . _:0b111ff8-3c48-254b-3aef-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0247 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-254c-3af0-f23c91a70cca . _:0b111ff8-3c48-254c-3af0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0248 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-20 Zone Temperature" ; ph:dis "Bravo VAV 2-20 Zone Temperature" ; phIoT:equipRef _:b-0241 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c48-254d-3af1-f23c91a70cca . _:0b111ff8-3c48-254d-3af1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0249 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-21" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c48-254e-3af2-f23c91a70cca . _:0b111ff8-3c48-254e-3af2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 10.4 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-024a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-21 Damper Output" ; ph:dis "Bravo VAV 2-21 Damper Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c48-254f-3af3-f23c91a70cca . _:0b111ff8-3c48-254f-3af3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-024b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2550-3af4-f23c91a70cca . _:0b111ff8-3c48-2550-3af4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-024c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c48-2551-3af5-f23c91a70cca . _:0b111ff8-3c48-2551-3af5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-024d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-21 Heating Valve Output" ; ph:dis "Bravo VAV 2-21 Heating Valve Output" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c48-2552-3af6-f23c91a70cca . _:0b111ff8-3c48-2552-3af6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-024e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-21 Supply Air Temperature" ; ph:dis "Bravo VAV 2-21 Supply Air Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-6780-3af7-f23c91a70cca . _:0b111ff8-3c57-6780-3af7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-024f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-6781-3af8-f23c91a70cca . _:0b111ff8-3c57-6781-3af8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0250 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-21 Zone Temperature" ; ph:dis "Bravo VAV 2-21 Zone Temperature" ; phIoT:equipRef _:b-0249 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-6782-3af9-f23c91a70cca . _:0b111ff8-3c57-6782-3af9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0251 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-22" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c57-6783-3afa-f23c91a70cca . _:0b111ff8-3c57-6783-3afa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0252 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-22 Damper Output" ; ph:dis "Bravo VAV 2-22 Damper Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c57-6784-3afb-f23c91a70cca . _:0b111ff8-3c57-6784-3afb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0253 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c57-6785-3afc-f23c91a70cca . _:0b111ff8-3c57-6785-3afc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0254 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c57-6786-3afd-f23c91a70cca . _:0b111ff8-3c57-6786-3afd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0255 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-22 Heating Valve Output" ; ph:dis "Bravo VAV 2-22 Heating Valve Output" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c57-6787-3afe-f23c91a70cca . _:0b111ff8-3c57-6787-3afe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0256 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-22 Supply Air Temperature" ; ph:dis "Bravo VAV 2-22 Supply Air Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-6788-3aff-f23c91a70cca . _:0b111ff8-3c57-6788-3aff-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0257 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-6789-3b00-f23c91a70cca . _:0b111ff8-3c57-6789-3b00-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0258 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-22 Zone Temperature" ; ph:dis "Bravo VAV 2-22 Zone Temperature" ; phIoT:equipRef _:b-0251 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c57-678a-3b01-f23c91a70cca . _:0b111ff8-3c57-678a-3b01-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0259 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-23" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c57-678b-3b02-f23c91a70cca . _:0b111ff8-3c57-678b-3b02-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 6.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-025a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-23 Damper Output" ; ph:dis "Bravo VAV 2-23 Damper Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c57-678c-3b03-f23c91a70cca . _:0b111ff8-3c57-678c-3b03-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-025b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c57-678d-3b04-f23c91a70cca . _:0b111ff8-3c57-678d-3b04-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-025c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c57-678e-3b05-f23c91a70cca . _:0b111ff8-3c57-678e-3b05-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-025d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-23 Heating Valve Output" ; ph:dis "Bravo VAV 2-23 Heating Valve Output" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c57-678f-3b06-f23c91a70cca . _:0b111ff8-3c57-678f-3b06-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-025e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-23 Supply Air Temperature" ; ph:dis "Bravo VAV 2-23 Supply Air Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c94-7080-3b07-f23c91a70cca . _:0b111ff8-3c94-7080-3b07-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-025f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c94-7081-3b08-f23c91a70cca . _:0b111ff8-3c94-7081-3b08-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0260 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-23 Zone Temperature" ; ph:dis "Bravo VAV 2-23 Zone Temperature" ; phIoT:equipRef _:b-0259 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c94-7082-3b09-f23c91a70cca . _:0b111ff8-3c94-7082-3b09-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0261 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-24" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3c94-7083-3b0a-f23c91a70cca . _:0b111ff8-3c94-7083-3b0a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 15.4 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1600 . _:b-0262 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-24 Damper Output" ; ph:dis "Bravo VAV 2-24 Damper Output" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c94-7084-3b0b-f23c91a70cca . _:0b111ff8-3c94-7084-3b0b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0263 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c94-7085-3b0c-f23c91a70cca . _:0b111ff8-3c94-7085-3b0c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0264 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3c94-7086-3b0d-f23c91a70cca . _:0b111ff8-3c94-7086-3b0d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0265 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-24 Heating Valve" ; ph:dis "Bravo VAV 2-24 Heating Valve" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3c94-7087-3b0e-f23c91a70cca . _:0b111ff8-3c94-7087-3b0e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0266 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-24 Supply Air Temperature" ; ph:dis "Bravo VAV 2-24 Supply Air Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c94-7088-3b0f-f23c91a70cca . _:0b111ff8-3c94-7088-3b0f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0267 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3c94-7089-3b10-f23c91a70cca . _:0b111ff8-3c94-7089-3b10-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0268 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-24 Zone Temperature" ; ph:dis "Bravo VAV 2-24 Zone Temperature" ; phIoT:equipRef _:b-0261 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2c0-3b11-f23c91a70cca . _:0b111ff8-3ca3-b2c0-3b11-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0269 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-25" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3ca3-b2c1-3b12-f23c91a70cca . _:0b111ff8-3ca3-b2c1-3b12-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 250 . _:b-026a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-25 Damper Output" ; ph:dis "Bravo VAV 2-25 Damper Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ca3-b2c2-3b13-f23c91a70cca . _:0b111ff8-3ca3-b2c2-3b13-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-026b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ca3-b2c3-3b14-f23c91a70cca . _:0b111ff8-3ca3-b2c3-3b14-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-026c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ca3-b2c4-3b15-f23c91a70cca . _:0b111ff8-3ca3-b2c4-3b15-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-026d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-25 Heating Valve Output" ; ph:dis "Bravo VAV 2-25 Heating Valve Output" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ca3-b2c5-3b16-f23c91a70cca . _:0b111ff8-3ca3-b2c5-3b16-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-026e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-25 Supply Air Temperature" ; ph:dis "Bravo VAV 2-25 Supply Air Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2c6-3b17-f23c91a70cca . _:0b111ff8-3ca3-b2c6-3b17-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-026f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2c7-3b18-f23c91a70cca . _:0b111ff8-3ca3-b2c7-3b18-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0270 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-25 Zone Temperature" ; ph:dis "Bravo VAV 2-25 Zone Temperature" ; phIoT:equipRef _:b-0269 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2c8-3b19-f23c91a70cca . _:0b111ff8-3ca3-b2c8-3b19-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0271 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-26" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3ca3-b2c9-3b1a-f23c91a70cca . _:0b111ff8-3ca3-b2c9-3b1a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 300 . _:b-0272 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-26 Damper Output" ; ph:dis "Bravo VAV 2-26 Damper Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ca3-b2ca-3b1b-f23c91a70cca . _:0b111ff8-3ca3-b2ca-3b1b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0273 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ca3-b2cb-3b1c-f23c91a70cca . _:0b111ff8-3ca3-b2cb-3b1c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0274 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ca3-b2cc-3b1d-f23c91a70cca . _:0b111ff8-3ca3-b2cc-3b1d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0275 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-26 Heating Valve Output" ; ph:dis "Bravo VAV 2-26 Heating Valve Output" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ca3-b2cd-3b1e-f23c91a70cca . _:0b111ff8-3ca3-b2cd-3b1e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0276 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-26 Supply Air Temperature" ; ph:dis "Bravo VAV 2-26 Supply Air Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2ce-3b1f-f23c91a70cca . _:0b111ff8-3ca3-b2ce-3b1f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0277 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2cf-3b20-f23c91a70cca . _:0b111ff8-3ca3-b2cf-3b20-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0278 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-26 Zone Temperature" ; ph:dis "Bravo VAV 2-26 Zone Temperature" ; phIoT:equipRef _:b-0271 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ca3-b2d0-3b21-f23c91a70cca . _:0b111ff8-3ca3-b2d0-3b21-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0279 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-27" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3ca3-b2d1-3b22-f23c91a70cca . _:0b111ff8-3ca3-b2d1-3b22-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 1125 . _:b-027a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-27 Damper Output" ; ph:dis "Bravo VAV 2-27 Damper Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cb2-f500-3b23-f23c91a70cca . _:0b111ff8-3cb2-f500-3b23-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-027b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f501-3b24-f23c91a70cca . _:0b111ff8-3cb2-f501-3b24-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f502-3b25-f23c91a70cca . _:0b111ff8-3cb2-f502-3b25-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-027d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-27 Heating Valve Output" ; ph:dis "Bravo VAV 2-27 Heating Valve Output" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cb2-f503-3b26-f23c91a70cca . _:0b111ff8-3cb2-f503-3b26-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-027e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-27 Supply Air Temperature" ; ph:dis "Bravo VAV 2-27 Supply Air Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f504-3b27-f23c91a70cca . _:0b111ff8-3cb2-f504-3b27-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-027f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f505-3b28-f23c91a70cca . _:0b111ff8-3cb2-f505-3b28-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0280 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-27 Zone Temperature" ; ph:dis "Bravo VAV 2-27 Zone Temperature" ; phIoT:equipRef _:b-0279 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f506-3b29-f23c91a70cca . _:0b111ff8-3cb2-f506-3b29-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0281 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-28" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3cb2-f507-3b2a-f23c91a70cca . _:0b111ff8-3cb2-f507-3b2a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-0282 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-28 Damper Output" ; ph:dis "Bravo VAV 2-28 Damper Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cb2-f508-3b2b-f23c91a70cca . _:0b111ff8-3cb2-f508-3b2b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0283 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f509-3b2c-f23c91a70cca . _:0b111ff8-3cb2-f509-3b2c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0284 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f50a-3b2d-f23c91a70cca . _:0b111ff8-3cb2-f50a-3b2d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0285 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-28 Heating Valve Output" ; ph:dis "Bravo VAV 2-28 Heating Valve Output" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cb2-f50b-3b2e-f23c91a70cca . _:0b111ff8-3cb2-f50b-3b2e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0286 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-28 Supply Air Temperature" ; ph:dis "Bravo VAV 2-28 Supply Air Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f50c-3b2f-f23c91a70cca . _:0b111ff8-3cb2-f50c-3b2f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0287 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f50d-3b30-f23c91a70cca . _:0b111ff8-3cb2-f50d-3b30-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0288 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-28 Zone Temperature" ; ph:dis "Bravo VAV 2-28 Zone Temperature" ; phIoT:equipRef _:b-0281 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cb2-f50e-3b31-f23c91a70cca . _:0b111ff8-3cb2-f50e-3b31-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0289 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-29" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-29" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3cb2-f50f-3b32-f23c91a70cca . _:0b111ff8-3cb2-f50f-3b32-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-028a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-29 Damper Output" ; ph:dis "Bravo VAV 2-29 Damper Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cb2-f510-3b33-f23c91a70cca . _:0b111ff8-3cb2-f510-3b33-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-028b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f511-3b34-f23c91a70cca . _:0b111ff8-3cb2-f511-3b34-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-028c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-29 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cb2-f512-3b35-f23c91a70cca . _:0b111ff8-3cb2-f512-3b35-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-028d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-29 Heating Valve Output" ; ph:dis "Bravo VAV 2-29 Heating Valve Output" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cc2-3740-3b36-f23c91a70cca . _:0b111ff8-3cc2-3740-3b36-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-028e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-29 Supply Air Temperature" ; ph:dis "Bravo VAV 2-29 Supply Air Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cc2-3741-3b37-f23c91a70cca . _:0b111ff8-3cc2-3741-3b37-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-028f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-29 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cc2-3742-3b38-f23c91a70cca . _:0b111ff8-3cc2-3742-3b38-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0290 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-29 Zone Temperature" ; ph:dis "Bravo VAV 2-29 Zone Temperature" ; phIoT:equipRef _:b-0289 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cc2-3743-3b39-f23c91a70cca . _:0b111ff8-3cc2-3743-3b39-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0291 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-3" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-3" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3cc2-3744-3b3a-f23c91a70cca . _:0b111ff8-3cc2-3744-3b3a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0292 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-3 Damper Output" ; ph:dis "Bravo VAV 2-3 Damper Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cc2-3745-3b3b-f23c91a70cca . _:0b111ff8-3cc2-3745-3b3b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0293 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cc2-3746-3b3c-f23c91a70cca . _:0b111ff8-3cc2-3746-3b3c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0294 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-3 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cc2-3747-3b3d-f23c91a70cca . _:0b111ff8-3cc2-3747-3b3d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0295 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-3 Heating Valve Output" ; ph:dis "Bravo VAV 2-3 Heating Valve Output" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cc2-3748-3b3e-f23c91a70cca . _:0b111ff8-3cc2-3748-3b3e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0296 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-3 Supply Air Temperature" ; ph:dis "Bravo VAV 2-3 Supply Air Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cef-fe00-3b3f-f23c91a70cca . _:0b111ff8-3cef-fe00-3b3f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0297 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-3 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cef-fe01-3b40-f23c91a70cca . _:0b111ff8-3cef-fe01-3b40-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0298 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-3 Zone Temperature" ; ph:dis "Bravo VAV 2-3 Zone Temperature" ; phIoT:equipRef _:b-0291 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-4040-3b41-f23c91a70cca . _:0b111ff8-3cff-4040-3b41-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0299 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-30" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-30" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3cff-4041-3b42-f23c91a70cca . _:0b111ff8-3cff-4041-3b42-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-029a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-30 Damper Output" ; ph:dis "Bravo VAV 2-30 Damper Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cff-4042-3b43-f23c91a70cca . _:0b111ff8-3cff-4042-3b43-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-029b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cff-4043-3b44-f23c91a70cca . _:0b111ff8-3cff-4043-3b44-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-029c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-30 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cff-4044-3b45-f23c91a70cca . _:0b111ff8-3cff-4044-3b45-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-029d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-30 Heating Valve Output" ; ph:dis "Bravo VAV 2-30 Heating Valve Output" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cff-4045-3b46-f23c91a70cca . _:0b111ff8-3cff-4045-3b46-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-029e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-30 Supply Air Temperature" ; ph:dis "Bravo VAV 2-30 Supply Air Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-4046-3b47-f23c91a70cca . _:0b111ff8-3cff-4046-3b47-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-029f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-30 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-4047-3b48-f23c91a70cca . _:0b111ff8-3cff-4047-3b48-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-30 Zone Temperature" ; ph:dis "Bravo VAV 2-30 Zone Temperature" ; phIoT:equipRef _:b-0299 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-4048-3b49-f23c91a70cca . _:0b111ff8-3cff-4048-3b49-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-31" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-31" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3cff-4049-3b4a-f23c91a70cca . _:0b111ff8-3cff-4049-3b4a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 18.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 650 . _:b-02a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-31 Damper Output" ; ph:dis "Bravo VAV 2-31 Damper Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cff-404a-3b4b-f23c91a70cca . _:0b111ff8-3cff-404a-3b4b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cff-404b-3b4c-f23c91a70cca . _:0b111ff8-3cff-404b-3b4c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-31 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3cff-404c-3b4d-f23c91a70cca . _:0b111ff8-3cff-404c-3b4d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-31 Heating Valve Output" ; ph:dis "Bravo VAV 2-31 Heating Valve Output" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3cff-404d-3b4e-f23c91a70cca . _:0b111ff8-3cff-404d-3b4e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-31 Supply Air Temperature" ; ph:dis "Bravo VAV 2-31 Supply Air Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-404e-3b4f-f23c91a70cca . _:0b111ff8-3cff-404e-3b4f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-31 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-404f-3b50-f23c91a70cca . _:0b111ff8-3cff-404f-3b50-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-31 Zone Temperature" ; ph:dis "Bravo VAV 2-31 Zone Temperature" ; phIoT:equipRef _:b-02a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3cff-4050-3b51-f23c91a70cca . _:0b111ff8-3cff-4050-3b51-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-32" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-32" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d0e-8280-3b52-f23c91a70cca . _:0b111ff8-3d0e-8280-3b52-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 28.6 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 2150 . _:b-02aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-32 Damper Output" ; ph:dis "Bravo VAV 2-32 Damper Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d0e-8281-3b53-f23c91a70cca . _:0b111ff8-3d0e-8281-3b53-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d0e-8282-3b54-f23c91a70cca . _:0b111ff8-3d0e-8282-3b54-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-32 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d0e-8283-3b55-f23c91a70cca . _:0b111ff8-3d0e-8283-3b55-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-32 Heating Valve Output" ; ph:dis "Bravo VAV 2-32 Heating Valve Output" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d0e-8284-3b56-f23c91a70cca . _:0b111ff8-3d0e-8284-3b56-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-32 Supply Air Temperature" ; ph:dis "Bravo VAV 2-32 Supply Air Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d0e-8285-3b57-f23c91a70cca . _:0b111ff8-3d0e-8285-3b57-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-32 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d0e-8286-3b58-f23c91a70cca . _:0b111ff8-3d0e-8286-3b58-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-32 Zone Temperature" ; ph:dis "Bravo VAV 2-32 Zone Temperature" ; phIoT:equipRef _:b-02a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d0e-8287-3b59-f23c91a70cca . _:0b111ff8-3d0e-8287-3b59-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-33" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-33" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d0e-8288-3b5a-f23c91a70cca . _:0b111ff8-3d0e-8288-3b5a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-02b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-33 Damper Output" ; ph:dis "Bravo VAV 2-33 Damper Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d0e-8289-3b5b-f23c91a70cca . _:0b111ff8-3d0e-8289-3b5b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d0e-828a-3b5c-f23c91a70cca . _:0b111ff8-3d0e-828a-3b5c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-33 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d0e-828b-3b5d-f23c91a70cca . _:0b111ff8-3d0e-828b-3b5d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-33 Heating Valve Output" ; ph:dis "Bravo VAV 2-33 Heating Valve Output" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d0e-828c-3b5e-f23c91a70cca . _:0b111ff8-3d0e-828c-3b5e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-33 Supply Air Temperature" ; ph:dis "Bravo VAV 2-33 Supply Air Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d0e-828d-3b5f-f23c91a70cca . _:0b111ff8-3d0e-828d-3b5f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-33 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d0e-828e-3b60-f23c91a70cca . _:0b111ff8-3d0e-828e-3b60-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-33 Zone Temperature" ; ph:dis "Bravo VAV 2-33 Zone Temperature" ; phIoT:equipRef _:b-02b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4c0-3b61-f23c91a70cca . _:0b111ff8-3d1d-c4c0-3b61-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-34" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-34" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d1d-c4c1-3b62-f23c91a70cca . _:0b111ff8-3d1d-c4c1-3b62-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 10.3 ; _:designHotWaterFlow 1 ; _:designAirFlow 575 . _:b-02ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-34 Damper Output" ; ph:dis "Bravo VAV 2-34 Damper Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d1d-c4c2-3b63-f23c91a70cca . _:0b111ff8-3d1d-c4c2-3b63-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d1d-c4c3-3b64-f23c91a70cca . _:0b111ff8-3d1d-c4c3-3b64-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-34 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d1d-c4c4-3b65-f23c91a70cca . _:0b111ff8-3d1d-c4c4-3b65-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-34 Heating Valve Output" ; ph:dis "Bravo VAV 2-34 Heating Valve Output" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d1d-c4c5-3b66-f23c91a70cca . _:0b111ff8-3d1d-c4c5-3b66-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-34 Supply Air Temperature" ; ph:dis "Bravo VAV 2-34 Supply Air Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4c6-3b67-f23c91a70cca . _:0b111ff8-3d1d-c4c6-3b67-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-34 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4c7-3b68-f23c91a70cca . _:0b111ff8-3d1d-c4c7-3b68-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-34 Zone Temperature" ; ph:dis "Bravo VAV 2-34 Zone Temperature" ; phIoT:equipRef _:b-02b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4c8-3b69-f23c91a70cca . _:0b111ff8-3d1d-c4c8-3b69-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-35" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-35" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d1d-c4c9-3b6a-f23c91a70cca . _:0b111ff8-3d1d-c4c9-3b6a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-35 Damper Output" ; ph:dis "Bravo VAV 2-35 Damper Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d1d-c4ca-3b6b-f23c91a70cca . _:0b111ff8-3d1d-c4ca-3b6b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d1d-c4cb-3b6c-f23c91a70cca . _:0b111ff8-3d1d-c4cb-3b6c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-02c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-35 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d1d-c4cc-3b6d-f23c91a70cca . _:0b111ff8-3d1d-c4cc-3b6d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-35 Heating Valve Output" ; ph:dis "Bravo VAV 2-35 Heating Valve Output" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d1d-c4cd-3b6e-f23c91a70cca . _:0b111ff8-3d1d-c4cd-3b6e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-35 Supply Air Temperature" ; ph:dis "Bravo VAV 2-35 Supply Air Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4ce-3b6f-f23c91a70cca . _:0b111ff8-3d1d-c4ce-3b6f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-35 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4cf-3b70-f23c91a70cca . _:0b111ff8-3d1d-c4cf-3b70-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-35 Zone Temperature" ; ph:dis "Bravo VAV 2-35 Zone Temperature" ; phIoT:equipRef _:b-02c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d1d-c4d0-3b71-f23c91a70cca . _:0b111ff8-3d1d-c4d0-3b71-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-36" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-36" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d1d-c4d1-3b72-f23c91a70cca . _:0b111ff8-3d1d-c4d1-3b72-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-02ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-36 Damper Output" ; ph:dis "Bravo VAV 2-36 Damper Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d1d-c4d2-3b73-f23c91a70cca . _:0b111ff8-3d1d-c4d2-3b73-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d2d-0700-3b74-f23c91a70cca . _:0b111ff8-3d2d-0700-3b74-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-02cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-36 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d2d-0701-3b75-f23c91a70cca . _:0b111ff8-3d2d-0701-3b75-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-36 Heating Valve Output" ; ph:dis "Bravo VAV 2-36 Heating Valve Output" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d2d-0702-3b76-f23c91a70cca . _:0b111ff8-3d2d-0702-3b76-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-02ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-36 Supply Air Temperature" ; ph:dis "Bravo VAV 2-36 Supply Air Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d5a-cdc0-3b77-f23c91a70cca . _:0b111ff8-3d5a-cdc0-3b77-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-36 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d5a-cdc1-3b78-f23c91a70cca . _:0b111ff8-3d5a-cdc1-3b78-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-36 Zone Temperature" ; ph:dis "Bravo VAV 2-36 Zone Temperature" ; phIoT:equipRef _:b-02c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d5a-cdc2-3b79-f23c91a70cca . _:0b111ff8-3d5a-cdc2-3b79-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-37" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-37" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d5a-cdc3-3b7a-f23c91a70cca . _:0b111ff8-3d5a-cdc3-3b7a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 10.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 500 . _:b-02d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-37 Damper Output" ; ph:dis "Bravo VAV 2-37 Damper Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d5a-cdc4-3b7b-f23c91a70cca . _:0b111ff8-3d5a-cdc4-3b7b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d5a-cdc5-3b7c-f23c91a70cca . _:0b111ff8-3d5a-cdc5-3b7c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-37 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d5a-cdc6-3b7d-f23c91a70cca . _:0b111ff8-3d5a-cdc6-3b7d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-37 Heating Valve Output" ; ph:dis "Bravo VAV 2-37 Heating Valve Output" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d6a-1000-3b7e-f23c91a70cca . _:0b111ff8-3d6a-1000-3b7e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-37 Supply Air Temperature" ; ph:dis "Bravo VAV 2-37 Supply Air Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-1001-3b7f-f23c91a70cca . _:0b111ff8-3d6a-1001-3b7f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-37 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-1002-3b80-f23c91a70cca . _:0b111ff8-3d6a-1002-3b80-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-37 Zone Temperature" ; ph:dis "Bravo VAV 2-37 Zone Temperature" ; phIoT:equipRef _:b-02d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-1003-3b81-f23c91a70cca . _:0b111ff8-3d6a-1003-3b81-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-02d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-38" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-38" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d6a-1004-3b82-f23c91a70cca . _:0b111ff8-3d6a-1004-3b82-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-02da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-38 Damper Output" ; ph:dis "Bravo VAV 2-38 Damper Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d6a-1005-3b83-f23c91a70cca . _:0b111ff8-3d6a-1005-3b83-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d6a-1006-3b84-f23c91a70cca . _:0b111ff8-3d6a-1006-3b84-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-02dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-38 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d6a-1007-3b85-f23c91a70cca . _:0b111ff8-3d6a-1007-3b85-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-38 Heating Valve Output" ; ph:dis "Bravo VAV 2-38 Heating Valve Output" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d6a-1008-3b86-f23c91a70cca . _:0b111ff8-3d6a-1008-3b86-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-38 Supply Air Temperature" ; ph:dis "Bravo VAV 2-38 Supply Air Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-1009-3b87-f23c91a70cca . _:0b111ff8-3d6a-1009-3b87-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-38 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-100a-3b88-f23c91a70cca . _:0b111ff8-3d6a-100a-3b88-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-38 Zone Temperature" ; ph:dis "Bravo VAV 2-38 Zone Temperature" ; phIoT:equipRef _:b-02d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d6a-100b-3b89-f23c91a70cca . _:0b111ff8-3d6a-100b-3b89-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-39" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-39" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d6a-100c-3b8a-f23c91a70cca . _:0b111ff8-3d6a-100c-3b8a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 9.5 ; _:designAirFlow 475 . _:b-02e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-39 Damper Output" ; ph:dis "Bravo VAV 2-39 Damper Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d6a-100d-3b8b-f23c91a70cca . _:0b111ff8-3d6a-100d-3b8b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d79-5240-3b8c-f23c91a70cca . _:0b111ff8-3d79-5240-3b8c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-02e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-39 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d79-5241-3b8d-f23c91a70cca . _:0b111ff8-3d79-5241-3b8d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-02e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-39 Heating Valve Output" ; ph:dis "Bravo VAV 2-39 Heating Valve Output" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d79-5242-3b8e-f23c91a70cca . _:0b111ff8-3d79-5242-3b8e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-39 Supply Air Temperature" ; ph:dis "Bravo VAV 2-39 Supply Air Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-5243-3b8f-f23c91a70cca . _:0b111ff8-3d79-5243-3b8f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-39 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-5244-3b90-f23c91a70cca . _:0b111ff8-3d79-5244-3b90-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-39 Zone Temperature" ; ph:dis "Bravo VAV 2-39 Zone Temperature" ; phIoT:equipRef _:b-02e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-5245-3b91-f23c91a70cca . _:0b111ff8-3d79-5245-3b91-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-4" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-4" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d79-5246-3b92-f23c91a70cca . _:0b111ff8-3d79-5246-3b92-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.9 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-02ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-4 Damper Output" ; ph:dis "Bravo VAV 2-4 Damper Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d79-5247-3b93-f23c91a70cca . _:0b111ff8-3d79-5247-3b93-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-02eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d79-5248-3b94-f23c91a70cca . _:0b111ff8-3d79-5248-3b94-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-4 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3d79-5249-3b95-f23c91a70cca . _:0b111ff8-3d79-5249-3b95-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-4 Heating Valve Output" ; ph:dis "Bravo VAV 2-4 Heating Valve Output" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3d79-524a-3b96-f23c91a70cca . _:0b111ff8-3d79-524a-3b96-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-4 Supply Air Temperature" ; ph:dis "Bravo VAV 2-4 Supply Air Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-524b-3b97-f23c91a70cca . _:0b111ff8-3d79-524b-3b97-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-4 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-524c-3b98-f23c91a70cca . _:0b111ff8-3d79-524c-3b98-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-02f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-4 Zone Temperature" ; ph:dis "Bravo VAV 2-4 Zone Temperature" ; phIoT:equipRef _:b-02e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3d79-524d-3b99-f23c91a70cca . _:0b111ff8-3d79-524d-3b99-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-40" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-40" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3d88-9480-3b9a-f23c91a70cca . _:0b111ff8-3d88-9480-3b9a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-40 Damper Output" ; ph:dis "Bravo VAV 2-40 Damper Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dc5-9d80-3b9b-f23c91a70cca . _:0b111ff8-3dc5-9d80-3b9b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dc5-9d81-3b9c-f23c91a70cca . _:0b111ff8-3dc5-9d81-3b9c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-40 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dc5-9d82-3b9d-f23c91a70cca . _:0b111ff8-3dc5-9d82-3b9d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-02f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-40 Heating Valve Output" ; ph:dis "Bravo VAV 2-40 Heating Valve Output" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dc5-9d83-3b9e-f23c91a70cca . _:0b111ff8-3dc5-9d83-3b9e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-02f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-40 Supply Air Temperature" ; ph:dis "Bravo VAV 2-40 Supply Air Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dc5-9d84-3b9f-f23c91a70cca . _:0b111ff8-3dc5-9d84-3b9f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-02f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-40 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dc5-9d85-3ba0-f23c91a70cca . _:0b111ff8-3dc5-9d85-3ba0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-02f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-40 Zone Temperature" ; ph:dis "Bravo VAV 2-40 Zone Temperature" ; phIoT:equipRef _:b-02f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dc5-9d86-3ba1-f23c91a70cca . _:0b111ff8-3dc5-9d86-3ba1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-02f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-41" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-41" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3dc5-9d87-3ba2-f23c91a70cca . _:0b111ff8-3dc5-9d87-3ba2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-02fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-41 Damper Output" ; ph:dis "Bravo VAV 2-41 Damper Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dc5-9d88-3ba3-f23c91a70cca . _:0b111ff8-3dc5-9d88-3ba3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.626-04:00"^^xsd:dateTime . _:b-02fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dc5-9d89-3ba4-f23c91a70cca . _:0b111ff8-3dc5-9d89-3ba4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-02fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-41 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dc5-9d8a-3ba5-f23c91a70cca . _:0b111ff8-3dc5-9d8a-3ba5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-02fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-41 Heating Valve Output" ; ph:dis "Bravo VAV 2-41 Heating Valve Output" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dc5-9d8b-3ba6-f23c91a70cca . _:0b111ff8-3dc5-9d8b-3ba6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-02fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-41 Supply Air Temperature" ; ph:dis "Bravo VAV 2-41 Supply Air Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfc0-3ba7-f23c91a70cca . _:0b111ff8-3dd4-dfc0-3ba7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-02ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-41 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfc1-3ba8-f23c91a70cca . _:0b111ff8-3dd4-dfc1-3ba8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0300 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-41 Zone Temperature" ; ph:dis "Bravo VAV 2-41 Zone Temperature" ; phIoT:equipRef _:b-02f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfc2-3ba9-f23c91a70cca . _:0b111ff8-3dd4-dfc2-3ba9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0301 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-42" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-42" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3dd4-dfc3-3baa-f23c91a70cca . _:0b111ff8-3dd4-dfc3-3baa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0302 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-42 Damper Output" ; ph:dis "Bravo VAV 2-42 Damper Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dd4-dfc4-3bab-f23c91a70cca . _:0b111ff8-3dd4-dfc4-3bab-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0303 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dd4-dfc5-3bac-f23c91a70cca . _:0b111ff8-3dd4-dfc5-3bac-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0304 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-42 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dd4-dfc6-3bad-f23c91a70cca . _:0b111ff8-3dd4-dfc6-3bad-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0305 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-42 Heating Valve Output" ; ph:dis "Bravo VAV 2-42 Heating Valve Output" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dd4-dfc7-3bae-f23c91a70cca . _:0b111ff8-3dd4-dfc7-3bae-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0306 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-42 Supply Air Temperature" ; ph:dis "Bravo VAV 2-42 Supply Air Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfc8-3baf-f23c91a70cca . _:0b111ff8-3dd4-dfc8-3baf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0307 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-42 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfc9-3bb0-f23c91a70cca . _:0b111ff8-3dd4-dfc9-3bb0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0308 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-42 Zone Temperature" ; ph:dis "Bravo VAV 2-42 Zone Temperature" ; phIoT:equipRef _:b-0301 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfca-3bb1-f23c91a70cca . _:0b111ff8-3dd4-dfca-3bb1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0309 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-43" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-43" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3dd4-dfcb-3bb2-f23c91a70cca . _:0b111ff8-3dd4-dfcb-3bb2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 141 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-030a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-43 Damper Output" ; ph:dis "Bravo VAV 2-43 Damper Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dd4-dfcc-3bb3-f23c91a70cca . _:0b111ff8-3dd4-dfcc-3bb3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-030b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dd4-dfcd-3bb4-f23c91a70cca . _:0b111ff8-3dd4-dfcd-3bb4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-43 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3dd4-dfce-3bb5-f23c91a70cca . _:0b111ff8-3dd4-dfce-3bb5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-030d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-43 Heating Valve Output" ; ph:dis "Bravo VAV 2-43 Heating Valve Output" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3dd4-dfcf-3bb6-f23c91a70cca . _:0b111ff8-3dd4-dfcf-3bb6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-030e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-43 Supply Air Temperature" ; ph:dis "Bravo VAV 2-43 Supply Air Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfd0-3bb7-f23c91a70cca . _:0b111ff8-3dd4-dfd0-3bb7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-030f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-43 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3dd4-dfd1-3bb8-f23c91a70cca . _:0b111ff8-3dd4-dfd1-3bb8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0310 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-43 Zone Temperature" ; ph:dis "Bravo VAV 2-43 Zone Temperature" ; phIoT:equipRef _:b-0309 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3de4-2200-3bb9-f23c91a70cca . _:0b111ff8-3de4-2200-3bb9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0311 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-44" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-44" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3de4-2201-3bba-f23c91a70cca . _:0b111ff8-3de4-2201-3bba-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.2 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-0312 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-44 Damper Output" ; ph:dis "Bravo VAV 2-44 Damper Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3de4-2202-3bbb-f23c91a70cca . _:0b111ff8-3de4-2202-3bbb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0313 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3de4-2203-3bbc-f23c91a70cca . _:0b111ff8-3de4-2203-3bbc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0314 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-44 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3de4-2204-3bbd-f23c91a70cca . _:0b111ff8-3de4-2204-3bbd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0315 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-44 Heating Valve Output" ; ph:dis "Bravo VAV 2-44 Heating Valve Output" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3de4-2205-3bbe-f23c91a70cca . _:0b111ff8-3de4-2205-3bbe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0316 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-44 Supply Air Temperature" ; ph:dis "Bravo VAV 2-44 Supply Air Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3de4-2206-3bbf-f23c91a70cca . _:0b111ff8-3de4-2206-3bbf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0317 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-44 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3de4-2207-3bc0-f23c91a70cca . _:0b111ff8-3de4-2207-3bc0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0318 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-44 Zone Temperature" ; ph:dis "Bravo VAV 2-44 Zone Temperature" ; phIoT:equipRef _:b-0311 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3de4-2208-3bc1-f23c91a70cca . _:0b111ff8-3de4-2208-3bc1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0319 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-45" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-45" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3de4-2209-3bc2-f23c91a70cca . _:0b111ff8-3de4-2209-3bc2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 17.8 ; _:designHotWaterFlow 1.75 ; _:designAirFlow 600 . _:b-031a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-45 Damper Output" ; ph:dis "Bravo VAV 2-45 Damper Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3de4-220a-3bc3-f23c91a70cca . _:0b111ff8-3de4-220a-3bc3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3de4-220b-3bc4-f23c91a70cca . _:0b111ff8-3de4-220b-3bc4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-031c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-45 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3de4-220c-3bc5-f23c91a70cca . _:0b111ff8-3de4-220c-3bc5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-031d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-45 Heating Valve Output" ; ph:dis "Bravo VAV 2-45 Heating Valve Output" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3de4-220d-3bc6-f23c91a70cca . _:0b111ff8-3de4-220d-3bc6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-031e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-45 Supply Air Temperature" ; ph:dis "Bravo VAV 2-45 Supply Air Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3df3-6440-3bc7-f23c91a70cca . _:0b111ff8-3df3-6440-3bc7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-031f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-45 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3df3-6441-3bc8-f23c91a70cca . _:0b111ff8-3df3-6441-3bc8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0320 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-45 Zone Temperature" ; ph:dis "Bravo VAV 2-45 Zone Temperature" ; phIoT:equipRef _:b-0319 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3df3-6442-3bc9-f23c91a70cca . _:0b111ff8-3df3-6442-3bc9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0321 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-46" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-46" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3df3-6443-3bca-f23c91a70cca . _:0b111ff8-3df3-6443-3bca-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0322 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-46 Damper Output" ; ph:dis "Bravo VAV 2-46 Damper Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3df3-6444-3bcb-f23c91a70cca . _:0b111ff8-3df3-6444-3bcb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0323 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3df3-6445-3bcc-f23c91a70cca . _:0b111ff8-3df3-6445-3bcc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0324 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-46 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e21-2b00-3bcd-f23c91a70cca . _:0b111ff8-3e21-2b00-3bcd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0325 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-46 Heating Valve Output" ; ph:dis "Bravo VAV 2-46 Heating Valve Output" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e21-2b01-3bce-f23c91a70cca . _:0b111ff8-3e21-2b01-3bce-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0326 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-46 Supply Air Temperature" ; ph:dis "Bravo VAV 2-46 Supply Air Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d40-3bcf-f23c91a70cca . _:0b111ff8-3e30-6d40-3bcf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0327 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-46 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d41-3bd0-f23c91a70cca . _:0b111ff8-3e30-6d41-3bd0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0328 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-46 Zone Temperature" ; ph:dis "Bravo VAV 2-46 Zone Temperature" ; phIoT:equipRef _:b-0321 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d42-3bd1-f23c91a70cca . _:0b111ff8-3e30-6d42-3bd1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0329 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-47" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-47" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e30-6d43-3bd2-f23c91a70cca . _:0b111ff8-3e30-6d43-3bd2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 25.9 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1400 . _:b-032a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-47 Damper Output" ; ph:dis "Bravo VAV 2-47 Damper Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e30-6d44-3bd3-f23c91a70cca . _:0b111ff8-3e30-6d44-3bd3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-032b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e30-6d45-3bd4-f23c91a70cca . _:0b111ff8-3e30-6d45-3bd4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-032c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-47 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e30-6d46-3bd5-f23c91a70cca . _:0b111ff8-3e30-6d46-3bd5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-47 Heating Valve Output" ; ph:dis "Bravo VAV 2-47 Heating Valve Output" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e30-6d47-3bd6-f23c91a70cca . _:0b111ff8-3e30-6d47-3bd6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-032e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-47 Supply Air Temperature" ; ph:dis "Bravo VAV 2-47 Supply Air Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d48-3bd7-f23c91a70cca . _:0b111ff8-3e30-6d48-3bd7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-032f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-47 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d49-3bd8-f23c91a70cca . _:0b111ff8-3e30-6d49-3bd8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0330 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-47 Zone Temperature" ; ph:dis "Bravo VAV 2-47 Zone Temperature" ; phIoT:equipRef _:b-0329 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e30-6d4a-3bd9-f23c91a70cca . _:0b111ff8-3e30-6d4a-3bd9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0331 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-48" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-48" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e30-6d4b-3bda-f23c91a70cca . _:0b111ff8-3e30-6d4b-3bda-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-0332 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-48 Damper Output" ; ph:dis "Bravo VAV 2-48 Damper Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e30-6d4c-3bdb-f23c91a70cca . _:0b111ff8-3e30-6d4c-3bdb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0333 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e30-6d4d-3bdc-f23c91a70cca . _:0b111ff8-3e30-6d4d-3bdc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-0334 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-48 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e3f-af80-3bdd-f23c91a70cca . _:0b111ff8-3e3f-af80-3bdd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0335 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-48 Heating Valve Output" ; ph:dis "Bravo VAV 2-48 Heating Valve Output" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e3f-af81-3bde-f23c91a70cca . _:0b111ff8-3e3f-af81-3bde-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0336 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-48 Supply Air Temperature" ; ph:dis "Bravo VAV 2-48 Supply Air Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af82-3bdf-f23c91a70cca . _:0b111ff8-3e3f-af82-3bdf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0337 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-48 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af83-3be0-f23c91a70cca . _:0b111ff8-3e3f-af83-3be0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0338 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-48 Zone Temperature" ; ph:dis "Bravo VAV 2-48 Zone Temperature" ; phIoT:equipRef _:b-0331 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af84-3be1-f23c91a70cca . _:0b111ff8-3e3f-af84-3be1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0339 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-49" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-49" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e3f-af85-3be2-f23c91a70cca . _:0b111ff8-3e3f-af85-3be2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-033a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-49 Damper Output" ; ph:dis "Bravo VAV 2-49 Damper Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e3f-af86-3be3-f23c91a70cca . _:0b111ff8-3e3f-af86-3be3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-033b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e3f-af87-3be4-f23c91a70cca . _:0b111ff8-3e3f-af87-3be4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-033c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-49 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e3f-af88-3be5-f23c91a70cca . _:0b111ff8-3e3f-af88-3be5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-033d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-49 Heating Valve Output" ; ph:dis "Bravo VAV 2-49 Heating Valve Output" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e3f-af89-3be6-f23c91a70cca . _:0b111ff8-3e3f-af89-3be6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-033e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-49 Supply Air Temperature" ; ph:dis "Bravo VAV 2-49 Supply Air Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af8a-3be7-f23c91a70cca . _:0b111ff8-3e3f-af8a-3be7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-033f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-49 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af8b-3be8-f23c91a70cca . _:0b111ff8-3e3f-af8b-3be8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0340 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-49 Zone Temperature" ; ph:dis "Bravo VAV 2-49 Zone Temperature" ; phIoT:equipRef _:b-0339 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e3f-af8c-3be9-f23c91a70cca . _:0b111ff8-3e3f-af8c-3be9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0341 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-5" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-5" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e3f-af8d-3bea-f23c91a70cca . _:0b111ff8-3e3f-af8d-3bea-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0342 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-5 Damper Output" ; ph:dis "Bravo VAV 2-5 Damper Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e4e-f1c0-3beb-f23c91a70cca . _:0b111ff8-3e4e-f1c0-3beb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0343 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e4e-f1c1-3bec-f23c91a70cca . _:0b111ff8-3e4e-f1c1-3bec-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0344 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-5 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e4e-f1c2-3bed-f23c91a70cca . _:0b111ff8-3e4e-f1c2-3bed-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0345 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-5 Heating Valve Output" ; ph:dis "Bravo VAV 2-5 Heating Valve Output" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e4e-f1c3-3bee-f23c91a70cca . _:0b111ff8-3e4e-f1c3-3bee-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0346 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-5 Supply Air Temperature" ; ph:dis "Bravo VAV 2-5 Supply Air Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1c4-3bef-f23c91a70cca . _:0b111ff8-3e4e-f1c4-3bef-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0347 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-5 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1c5-3bf0-f23c91a70cca . _:0b111ff8-3e4e-f1c5-3bf0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0348 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-5 Zone Temperature" ; ph:dis "Bravo VAV 2-5 Zone Temperature" ; phIoT:equipRef _:b-0341 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1c6-3bf1-f23c91a70cca . _:0b111ff8-3e4e-f1c6-3bf1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-0349 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-50" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-50" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e4e-f1c7-3bf2-f23c91a70cca . _:0b111ff8-3e4e-f1c7-3bf2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 475 . _:b-034a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-50 Damper Output" ; ph:dis "Bravo VAV 2-50 Damper Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e4e-f1c8-3bf3-f23c91a70cca . _:0b111ff8-3e4e-f1c8-3bf3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-034b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e4e-f1c9-3bf4-f23c91a70cca . _:0b111ff8-3e4e-f1c9-3bf4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-034c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-50 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e4e-f1ca-3bf5-f23c91a70cca . _:0b111ff8-3e4e-f1ca-3bf5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-034d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-50 Heating Valve Output" ; ph:dis "Bravo VAV 2-50 Heating Valve Output" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e4e-f1cb-3bf6-f23c91a70cca . _:0b111ff8-3e4e-f1cb-3bf6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-034e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-50 Supply Air Temperature" ; ph:dis "Bravo VAV 2-50 Supply Air Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1cc-3bf7-f23c91a70cca . _:0b111ff8-3e4e-f1cc-3bf7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-034f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-50 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1cd-3bf8-f23c91a70cca . _:0b111ff8-3e4e-f1cd-3bf8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0350 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-50 Zone Temperature" ; ph:dis "Bravo VAV 2-50 Zone Temperature" ; phIoT:equipRef _:b-0349 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e4e-f1ce-3bf9-f23c91a70cca . _:0b111ff8-3e4e-f1ce-3bf9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0351 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-6" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-6" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e5e-3400-3bfa-f23c91a70cca . _:0b111ff8-3e5e-3400-3bfa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 148 ; _:designHotWaterPower 4.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 350 . _:b-0352 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-6 Damper Output" ; ph:dis "Bravo VAV 2-6 Damper Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e5e-3401-3bfb-f23c91a70cca . _:0b111ff8-3e5e-3401-3bfb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0353 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e5e-3402-3bfc-f23c91a70cca . _:0b111ff8-3e5e-3402-3bfc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-0354 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-6 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e5e-3403-3bfd-f23c91a70cca . _:0b111ff8-3e5e-3403-3bfd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0355 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-6 Heating Valve Output" ; ph:dis "Bravo VAV 2-6 Heating Valve Output" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e8b-fac0-3bfe-f23c91a70cca . _:0b111ff8-3e8b-fac0-3bfe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0356 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-6 Supply Air Temperature" ; ph:dis "Bravo VAV 2-6 Supply Air Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e8b-fac1-3bff-f23c91a70cca . _:0b111ff8-3e8b-fac1-3bff-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0357 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-6 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e8b-fac2-3c00-f23c91a70cca . _:0b111ff8-3e8b-fac2-3c00-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0358 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-6 Zone Temperature" ; ph:dis "Bravo VAV 2-6 Zone Temperature" ; phIoT:equipRef _:b-0351 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e8b-fac3-3c01-f23c91a70cca . _:0b111ff8-3e8b-fac3-3c01-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0359 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-7" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-7" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e8b-fac4-3c02-f23c91a70cca . _:0b111ff8-3e8b-fac4-3c02-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 10 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 650 . _:b-035a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-7 Damper Output" ; ph:dis "Bravo VAV 2-7 Damper Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e8b-fac5-3c03-f23c91a70cca . _:0b111ff8-3e8b-fac5-3c03-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-035b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e8b-fac6-3c04-f23c91a70cca . _:0b111ff8-3e8b-fac6-3c04-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-035c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-7 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e9b-3d00-3c05-f23c91a70cca . _:0b111ff8-3e9b-3d00-3c05-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-035d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-7 Heating Valve Output" ; ph:dis "Bravo VAV 2-7 Heating Valve Output" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e9b-3d01-3c06-f23c91a70cca . _:0b111ff8-3e9b-3d01-3c06-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-035e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-7 Supply Air Temperature" ; ph:dis "Bravo VAV 2-7 Supply Air Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d02-3c07-f23c91a70cca . _:0b111ff8-3e9b-3d02-3c07-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-035f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-7 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d03-3c08-f23c91a70cca . _:0b111ff8-3e9b-3d03-3c08-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0360 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-7 Zone Temperature" ; ph:dis "Bravo VAV 2-7 Zone Temperature" ; phIoT:equipRef _:b-0359 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d04-3c09-f23c91a70cca . _:0b111ff8-3e9b-3d04-3c09-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0361 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-8" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-8" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e9b-3d05-3c0a-f23c91a70cca . _:0b111ff8-3e9b-3d05-3c0a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0362 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-8 Damper Output" ; ph:dis "Bravo VAV 2-8 Damper Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e9b-3d06-3c0b-f23c91a70cca . _:0b111ff8-3e9b-3d06-3c0b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0363 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e9b-3d07-3c0c-f23c91a70cca . _:0b111ff8-3e9b-3d07-3c0c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0364 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-8 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e9b-3d08-3c0d-f23c91a70cca . _:0b111ff8-3e9b-3d08-3c0d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0365 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-8 Heating Valve Output" ; ph:dis "Bravo VAV 2-8 Heating Valve Output" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e9b-3d09-3c0e-f23c91a70cca . _:0b111ff8-3e9b-3d09-3c0e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0366 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-8 Supply Air Temperature" ; ph:dis "Bravo VAV 2-8 Supply Air Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d0a-3c0f-f23c91a70cca . _:0b111ff8-3e9b-3d0a-3c0f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0367 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-8 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d0b-3c10-f23c91a70cca . _:0b111ff8-3e9b-3d0b-3c10-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0368 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-8 Zone Temperature" ; ph:dis "Bravo VAV 2-8 Zone Temperature" ; phIoT:equipRef _:b-0361 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d0c-3c11-f23c91a70cca . _:0b111ff8-3e9b-3d0c-3c11-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0369 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 2-9" ; phIoT:airRef _:b-00ce ; ph:dis "Bravo VAV 2-9" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3e9b-3d0d-3c12-f23c91a70cca . _:0b111ff8-3e9b-3d0d-3c12-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.9 ; _:designHotWaterFlow 1 ; _:designAirFlow 450 . _:b-036a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 2-9 Damper Output" ; ph:dis "Bravo VAV 2-9 Damper Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e9b-3d0e-3c13-f23c91a70cca . _:0b111ff8-3e9b-3d0e-3c13-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-036b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e9b-3d0f-3c14-f23c91a70cca . _:0b111ff8-3e9b-3d0f-3c14-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-036c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 2-9 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3e9b-3d10-3c15-f23c91a70cca . _:0b111ff8-3e9b-3d10-3c15-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-036d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 2-9 Heating Valve Output" ; ph:dis "Bravo VAV 2-9 Heating Valve Output" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3e9b-3d11-3c16-f23c91a70cca . _:0b111ff8-3e9b-3d11-3c16-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 2-9 Supply Air Temperature" ; ph:dis "Bravo VAV 2-9 Supply Air Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3e9b-3d12-3c17-f23c91a70cca . _:0b111ff8-3e9b-3d12-3c17-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-036f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 2-9 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f40-3c18-f23c91a70cca . _:0b111ff8-3eaa-7f40-3c18-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0370 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 2-9 Zone Temperature" ; ph:dis "Bravo VAV 2-9 Zone Temperature" ; phIoT:equipRef _:b-0369 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f41-3c19-f23c91a70cca . _:0b111ff8-3eaa-7f41-3c19-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0371 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-1" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-1" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3eaa-7f42-3c1a-f23c91a70cca . _:0b111ff8-3eaa-7f42-3c1a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 14.1 ; _:designHotWaterFlow 2.5 ; _:designAirFlow 1300 . _:b-0372 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-1 Air Damper Command" ; ph:dis "Bravo VAV 3-1 Air Damper Command" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eaa-7f43-3c1b-f23c91a70cca . _:0b111ff8-3eaa-7f43-3c1b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime ; _:pointType "" . _:b-0373 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eaa-7f44-3c1c-f23c91a70cca . _:0b111ff8-3eaa-7f44-3c1c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0374 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-1 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eaa-7f45-3c1d-f23c91a70cca . _:0b111ff8-3eaa-7f45-3c1d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-0375 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-1 Heating Valve Output" ; ph:dis "Bravo VAV 3-1 Heating Valve Output" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eaa-7f46-3c1e-f23c91a70cca . _:0b111ff8-3eaa-7f46-3c1e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0376 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-1 Supply Air Temperature" ; ph:dis "Bravo VAV 3-1 Supply Air Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f47-3c1f-f23c91a70cca . _:0b111ff8-3eaa-7f47-3c1f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0377 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-1 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f48-3c20-f23c91a70cca . _:0b111ff8-3eaa-7f48-3c20-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0378 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-1 Zone Temperature" ; ph:dis "Bravo VAV 3-1 Zone Temperature" ; phIoT:equipRef _:b-0371 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f49-3c21-f23c91a70cca . _:0b111ff8-3eaa-7f49-3c21-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0379 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-10" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-10" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3eaa-7f4a-3c22-f23c91a70cca . _:0b111ff8-3eaa-7f4a-3c22-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 7.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-037a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-10 Damper Output" ; ph:dis "Bravo VAV 3-10 Damper Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eaa-7f4b-3c23-f23c91a70cca . _:0b111ff8-3eaa-7f4b-3c23-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-037b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eaa-7f4c-3c24-f23c91a70cca . _:0b111ff8-3eaa-7f4c-3c24-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-037c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-10 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eaa-7f4d-3c25-f23c91a70cca . _:0b111ff8-3eaa-7f4d-3c25-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-037d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-10 Heating Valve Output" ; ph:dis "Bravo VAV 3-10 Heating Valve Output" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eaa-7f4e-3c26-f23c91a70cca . _:0b111ff8-3eaa-7f4e-3c26-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-037e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-10 Supply Air Temperature" ; ph:dis "Bravo VAV 3-10 Supply Air Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f4f-3c27-f23c91a70cca . _:0b111ff8-3eaa-7f4f-3c27-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-037f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-10 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f50-3c28-f23c91a70cca . _:0b111ff8-3eaa-7f50-3c28-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0380 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-10 Zone Temperature" ; ph:dis "Bravo VAV 3-10 Zone Temperature" ; phIoT:equipRef _:b-0379 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eaa-7f51-3c29-f23c91a70cca . _:0b111ff8-3eaa-7f51-3c29-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0381 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-11" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-11" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3eb9-c180-3c2a-f23c91a70cca . _:0b111ff8-3eb9-c180-3c2a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 22.7 ; _:designHotWaterFlow 2.25 ; _:designAirFlow 1100 . _:b-0382 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-11 Damper Output" ; ph:dis "Bravo VAV 3-11 Damper Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eb9-c181-3c2b-f23c91a70cca . _:0b111ff8-3eb9-c181-3c2b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0383 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eb9-c182-3c2c-f23c91a70cca . _:0b111ff8-3eb9-c182-3c2c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0384 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-11 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eb9-c183-3c2d-f23c91a70cca . _:0b111ff8-3eb9-c183-3c2d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0385 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-11 Heating Valve Output" ; ph:dis "Bravo VAV 3-11 Heating Valve Output" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eb9-c184-3c2e-f23c91a70cca . _:0b111ff8-3eb9-c184-3c2e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0386 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-11 Supply Air Temperature" ; ph:dis "Bravo VAV 3-11 Supply Air Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c185-3c2f-f23c91a70cca . _:0b111ff8-3eb9-c185-3c2f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0387 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-11 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c186-3c30-f23c91a70cca . _:0b111ff8-3eb9-c186-3c30-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-0388 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-11 Zone Temperature" ; ph:dis "Bravo VAV 3-11 Zone Temperature" ; phIoT:equipRef _:b-0381 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c187-3c31-f23c91a70cca . _:0b111ff8-3eb9-c187-3c31-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0389 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-12" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-12" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3eb9-c188-3c32-f23c91a70cca . _:0b111ff8-3eb9-c188-3c32-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 9.8 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 1000 . _:b-038a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-12 Damper Output" ; ph:dis "Bravo VAV 3-12 Damper Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eb9-c189-3c33-f23c91a70cca . _:0b111ff8-3eb9-c189-3c33-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-038b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eb9-c18a-3c34-f23c91a70cca . _:0b111ff8-3eb9-c18a-3c34-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-038c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-12 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3eb9-c18b-3c35-f23c91a70cca . _:0b111ff8-3eb9-c18b-3c35-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-038d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-12 Heating Valve Output" ; ph:dis "Bravo VAV 3-12 Heating Valve Output" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3eb9-c18c-3c36-f23c91a70cca . _:0b111ff8-3eb9-c18c-3c36-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-038e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-12 Supply Air Temperature" ; ph:dis "Bravo VAV 3-12 Supply Air Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c18d-3c37-f23c91a70cca . _:0b111ff8-3eb9-c18d-3c37-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-038f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-12 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c18e-3c38-f23c91a70cca . _:0b111ff8-3eb9-c18e-3c38-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0390 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-12 Zone Temperature" ; ph:dis "Bravo VAV 3-12 Zone Temperature" ; phIoT:equipRef _:b-0389 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3eb9-c18f-3c39-f23c91a70cca . _:0b111ff8-3eb9-c18f-3c39-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0391 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-13" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-13" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3ef6-ca80-3c3a-f23c91a70cca . _:0b111ff8-3ef6-ca80-3c3a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 5.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 350 . _:b-0392 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-13 Damper Output" ; ph:dis "Bravo VAV 3-13 Damper Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ef6-ca81-3c3b-f23c91a70cca . _:0b111ff8-3ef6-ca81-3c3b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0393 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ef6-ca82-3c3c-f23c91a70cca . _:0b111ff8-3ef6-ca82-3c3c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0394 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-13 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ef6-ca83-3c3d-f23c91a70cca . _:0b111ff8-3ef6-ca83-3c3d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0395 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-13 Heating Valve Output" ; ph:dis "Bravo VAV 3-13 Heating Valve Output" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ef6-ca84-3c3e-f23c91a70cca . _:0b111ff8-3ef6-ca84-3c3e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-0396 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-13 Supply Air Temperature" ; ph:dis "Bravo VAV 3-13 Supply Air Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ef6-ca85-3c3f-f23c91a70cca . _:0b111ff8-3ef6-ca85-3c3f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0397 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-13 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ef6-ca86-3c40-f23c91a70cca . _:0b111ff8-3ef6-ca86-3c40-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-0398 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-13 Zone Temperature" ; ph:dis "Bravo VAV 3-13 Zone Temperature" ; phIoT:equipRef _:b-0391 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3ef6-ca87-3c41-f23c91a70cca . _:0b111ff8-3ef6-ca87-3c41-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0399 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-14" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-14" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3ef6-ca88-3c42-f23c91a70cca . _:0b111ff8-3ef6-ca88-3c42-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 5.4 ; _:designHotWaterFlow 1 ; _:designAirFlow 500 . _:b-039a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-14 Damper Output" ; ph:dis "Bravo VAV 3-14 Damper Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3ef6-ca89-3c43-f23c91a70cca . _:0b111ff8-3ef6-ca89-3c43-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-039b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3ef6-ca8a-3c44-f23c91a70cca . _:0b111ff8-3ef6-ca8a-3c44-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-039c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-14 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f06-0cc0-3c45-f23c91a70cca . _:0b111ff8-3f06-0cc0-3c45-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-039d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-14 Heating Valve Output" ; ph:dis "Bravo VAV 3-14 Heating Valve Output" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f06-0cc1-3c46-f23c91a70cca . _:0b111ff8-3f06-0cc1-3c46-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-039e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-14 Supply Air Temperature" ; ph:dis "Bravo VAV 3-14 Supply Air Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0cc2-3c47-f23c91a70cca . _:0b111ff8-3f06-0cc2-3c47-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-039f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-14 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0cc3-3c48-f23c91a70cca . _:0b111ff8-3f06-0cc3-3c48-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03a0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-14 Zone Temperature" ; ph:dis "Bravo VAV 3-14 Zone Temperature" ; phIoT:equipRef _:b-0399 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0cc4-3c49-f23c91a70cca . _:0b111ff8-3f06-0cc4-3c49-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03a1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-15" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-15" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f06-0cc5-3c4a-f23c91a70cca . _:0b111ff8-3f06-0cc5-3c4a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 147 ; _:designHotWaterPower 2.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 250 . _:b-03a2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-15 Damper Output" ; ph:dis "Bravo VAV 3-15 Damper Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f06-0cc6-3c4b-f23c91a70cca . _:0b111ff8-3f06-0cc6-3c4b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03a3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f06-0cc7-3c4c-f23c91a70cca . _:0b111ff8-3f06-0cc7-3c4c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03a4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-15 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f06-0cc8-3c4d-f23c91a70cca . _:0b111ff8-3f06-0cc8-3c4d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-15 Heating Valve Output" ; ph:dis "Bravo VAV 3-15 Heating Valve Output" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f06-0cc9-3c4e-f23c91a70cca . _:0b111ff8-3f06-0cc9-3c4e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-15 Supply Air Temperature" ; ph:dis "Bravo VAV 3-15 Supply Air Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0cca-3c4f-f23c91a70cca . _:0b111ff8-3f06-0cca-3c4f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-03a7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-15 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0ccb-3c50-f23c91a70cca . _:0b111ff8-3f06-0ccb-3c50-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03a8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-15 Zone Temperature" ; ph:dis "Bravo VAV 3-15 Zone Temperature" ; phIoT:equipRef _:b-03a1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f06-0ccc-3c51-f23c91a70cca . _:0b111ff8-3f06-0ccc-3c51-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03a9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-16" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-16" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f06-0ccd-3c52-f23c91a70cca . _:0b111ff8-3f06-0ccd-3c52-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03aa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-16 Damper Output" ; ph:dis "Bravo VAV 3-16 Damper Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f06-0cce-3c53-f23c91a70cca . _:0b111ff8-3f06-0cce-3c53-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ab a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f15-4f00-3c54-f23c91a70cca . _:0b111ff8-3f15-4f00-3c54-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03ac a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-16 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f15-4f01-3c55-f23c91a70cca . _:0b111ff8-3f15-4f01-3c55-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03ad a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-16 Heating Valve Output" ; ph:dis "Bravo VAV 3-16 Heating Valve Output" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f15-4f02-3c56-f23c91a70cca . _:0b111ff8-3f15-4f02-3c56-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03ae a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-16 Supply Air Temperature" ; ph:dis "Bravo VAV 3-16 Supply Air Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f03-3c57-f23c91a70cca . _:0b111ff8-3f15-4f03-3c57-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03af a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-16 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f04-3c58-f23c91a70cca . _:0b111ff8-3f15-4f04-3c58-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03b0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-16 Zone Temperature" ; ph:dis "Bravo VAV 3-16 Zone Temperature" ; phIoT:equipRef _:b-03a9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f05-3c59-f23c91a70cca . _:0b111ff8-3f15-4f05-3c59-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-17" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-17" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f15-4f06-3c5a-f23c91a70cca . _:0b111ff8-3f15-4f06-3c5a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03b2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-17 Damper Output" ; ph:dis "Bravo VAV 3-17 Damper Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f15-4f07-3c5b-f23c91a70cca . _:0b111ff8-3f15-4f07-3c5b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03b3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f15-4f08-3c5c-f23c91a70cca . _:0b111ff8-3f15-4f08-3c5c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03b4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-17 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f15-4f09-3c5d-f23c91a70cca . _:0b111ff8-3f15-4f09-3c5d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-17 Heating Valve Output" ; ph:dis "Bravo VAV 3-17 Heating Valve Output" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f15-4f0a-3c5e-f23c91a70cca . _:0b111ff8-3f15-4f0a-3c5e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03b6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-17 Supply Air Temperature" ; ph:dis "Bravo VAV 3-17 Supply Air Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f0b-3c5f-f23c91a70cca . _:0b111ff8-3f15-4f0b-3c5f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-17 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f0c-3c60-f23c91a70cca . _:0b111ff8-3f15-4f0c-3c60-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03b8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-17 Zone Temperature" ; ph:dis "Bravo VAV 3-17 Zone Temperature" ; phIoT:equipRef _:b-03b1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f15-4f0d-3c61-f23c91a70cca . _:0b111ff8-3f15-4f0d-3c61-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03b9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-18" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-18" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f15-4f0e-3c62-f23c91a70cca . _:0b111ff8-3f15-4f0e-3c62-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 12.4 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 500 . _:b-03ba a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-18 Damper Output" ; ph:dis "Bravo VAV 3-18 Damper Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f15-4f0f-3c63-f23c91a70cca . _:0b111ff8-3f15-4f0f-3c63-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03bb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f15-4f10-3c64-f23c91a70cca . _:0b111ff8-3f15-4f10-3c64-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03bc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-18 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f24-9140-3c65-f23c91a70cca . _:0b111ff8-3f24-9140-3c65-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03bd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-18 Heating Valve Output" ; ph:dis "Bravo VAV 3-18 Heating Valve Output" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f24-9141-3c66-f23c91a70cca . _:0b111ff8-3f24-9141-3c66-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03be a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-18 Supply Air Temperature" ; ph:dis "Bravo VAV 3-18 Supply Air Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f24-9142-3c67-f23c91a70cca . _:0b111ff8-3f24-9142-3c67-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03bf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-18 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f24-9143-3c68-f23c91a70cca . _:0b111ff8-3f24-9143-3c68-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03c0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-18 Zone Temperature" ; ph:dis "Bravo VAV 3-18 Zone Temperature" ; phIoT:equipRef _:b-03b9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f24-9144-3c69-f23c91a70cca . _:0b111ff8-3f24-9144-3c69-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-19" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-19" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f24-9145-3c6a-f23c91a70cca . _:0b111ff8-3f24-9145-3c6a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 2.1 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-03c2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-19 Damper Output" ; ph:dis "Bravo VAV 3-19 Damper Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f24-9146-3c6b-f23c91a70cca . _:0b111ff8-3f24-9146-3c6b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-03c3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f24-9147-3c6c-f23c91a70cca . _:0b111ff8-3f24-9147-3c6c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03c4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-19 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f24-9148-3c6d-f23c91a70cca . _:0b111ff8-3f24-9148-3c6d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03c5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-19 Heating Valve Output" ; ph:dis "Bravo VAV 3-19 Heating Valve Output" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f24-9149-3c6e-f23c91a70cca . _:0b111ff8-3f24-9149-3c6e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-03c6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-19 Supply Air Temperature" ; ph:dis "Bravo VAV 3-19 Supply Air Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f52-5800-3c6f-f23c91a70cca . _:0b111ff8-3f52-5800-3c6f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03c7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-19 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f52-5801-3c70-f23c91a70cca . _:0b111ff8-3f52-5801-3c70-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03c8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-19 Zone Temperature" ; ph:dis "Bravo VAV 3-19 Zone Temperature" ; phIoT:equipRef _:b-03c1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a40-3c71-f23c91a70cca . _:0b111ff8-3f61-9a40-3c71-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03c9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-2" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-2" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f61-9a41-3c72-f23c91a70cca . _:0b111ff8-3f61-9a41-3c72-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 8.7 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 800 . _:b-03ca a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-2 Damper Output" ; ph:dis "Bravo VAV 3-2 Damper Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f61-9a42-3c73-f23c91a70cca . _:0b111ff8-3f61-9a42-3c73-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03cb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f61-9a43-3c74-f23c91a70cca . _:0b111ff8-3f61-9a43-3c74-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03cc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-2 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f61-9a44-3c75-f23c91a70cca . _:0b111ff8-3f61-9a44-3c75-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03cd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-2 Heating Valve Output" ; ph:dis "Bravo VAV 3-2 Heating Valve Output" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f61-9a45-3c76-f23c91a70cca . _:0b111ff8-3f61-9a45-3c76-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03ce a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-2 Supply Air Temperature" ; ph:dis "Bravo VAV 3-2 Supply Air Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a46-3c77-f23c91a70cca . _:0b111ff8-3f61-9a46-3c77-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03cf a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-2 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a47-3c78-f23c91a70cca . _:0b111ff8-3f61-9a47-3c78-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-2 Zone Temperature" ; ph:dis "Bravo VAV 3-2 Zone Temperature" ; phIoT:equipRef _:b-03c9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a48-3c79-f23c91a70cca . _:0b111ff8-3f61-9a48-3c79-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03d1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-20" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-20" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f61-9a49-3c7a-f23c91a70cca . _:0b111ff8-3f61-9a49-3c7a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 4.1 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03d2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-20 Damper Output" ; ph:dis "Bravo VAV 3-20 Damper Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f61-9a4a-3c7b-f23c91a70cca . _:0b111ff8-3f61-9a4a-3c7b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03d3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f61-9a4b-3c7c-f23c91a70cca . _:0b111ff8-3f61-9a4b-3c7c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-20 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f61-9a4c-3c7d-f23c91a70cca . _:0b111ff8-3f61-9a4c-3c7d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03d5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-20 Heating Valve Output" ; ph:dis "Bravo VAV 3-20 Heating Valve Output" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f61-9a4d-3c7e-f23c91a70cca . _:0b111ff8-3f61-9a4d-3c7e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03d6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-20 Supply Air Temperature" ; ph:dis "Bravo VAV 3-20 Supply Air Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a4e-3c7f-f23c91a70cca . _:0b111ff8-3f61-9a4e-3c7f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-20 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a4f-3c80-f23c91a70cca . _:0b111ff8-3f61-9a4f-3c80-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03d8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-20 Zone Temperature" ; ph:dis "Bravo VAV 3-20 Zone Temperature" ; phIoT:equipRef _:b-03d1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f61-9a50-3c81-f23c91a70cca . _:0b111ff8-3f61-9a50-3c81-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03d9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-21" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-21" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f61-9a51-3c82-f23c91a70cca . _:0b111ff8-3f61-9a51-3c82-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1 ; _:designAirFlow 300 . _:b-03da a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-21 Damper Output" ; ph:dis "Bravo VAV 3-21 Damper Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f70-dc80-3c83-f23c91a70cca . _:0b111ff8-3f70-dc80-3c83-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-03db a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f70-dc81-3c84-f23c91a70cca . _:0b111ff8-3f70-dc81-3c84-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:11.258-04:00"^^xsd:dateTime . _:b-03dc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-21 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f70-dc82-3c85-f23c91a70cca . _:0b111ff8-3f70-dc82-3c85-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03dd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-21 Heating Valve Output" ; ph:dis "Bravo VAV 3-21 Heating Valve Output" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f70-dc83-3c86-f23c91a70cca . _:0b111ff8-3f70-dc83-3c86-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03de a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-21 Supply Air Temperature" ; ph:dis "Bravo VAV 3-21 Supply Air Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f70-dc84-3c87-f23c91a70cca . _:0b111ff8-3f70-dc84-3c87-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03df a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-21 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f70-dc85-3c88-f23c91a70cca . _:0b111ff8-3f70-dc85-3c88-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-21 Zone Temperature" ; ph:dis "Bravo VAV 3-21 Zone Temperature" ; phIoT:equipRef _:b-03d9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f70-dc86-3c89-f23c91a70cca . _:0b111ff8-3f70-dc86-3c89-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-03e1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-22" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-22" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f70-dc87-3c8a-f23c91a70cca . _:0b111ff8-3f70-dc87-3c8a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 29.2 ; _:designHotWaterFlow 3.5 ; _:designAirFlow 1250 . _:b-03e2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-22 Damper Output" ; ph:dis "Bravo VAV 3-22 Damper Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f70-dc88-3c8b-f23c91a70cca . _:0b111ff8-3f70-dc88-3c8b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03e3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f70-dc89-3c8c-f23c91a70cca . _:0b111ff8-3f70-dc89-3c8c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03e4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-22 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f70-dc8a-3c8d-f23c91a70cca . _:0b111ff8-3f70-dc8a-3c8d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-22 Heating Valve Output" ; ph:dis "Bravo VAV 3-22 Heating Valve Output" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f70-dc8b-3c8e-f23c91a70cca . _:0b111ff8-3f70-dc8b-3c8e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03e6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-22 Supply Air Temperature" ; ph:dis "Bravo VAV 3-22 Supply Air Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f70-dc8c-3c8f-f23c91a70cca . _:0b111ff8-3f70-dc8c-3c8f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-03e7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-22 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f70-dc8d-3c90-f23c91a70cca . _:0b111ff8-3f70-dc8d-3c90-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-03e8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-22 Zone Temperature" ; ph:dis "Bravo VAV 3-22 Zone Temperature" ; phIoT:equipRef _:b-03e1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ec0-3c91-f23c91a70cca . _:0b111ff8-3f80-1ec0-3c91-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03e9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-23" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-23" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f80-1ec1-3c92-f23c91a70cca . _:0b111ff8-3f80-1ec1-3c92-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 2.2 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-03ea a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-23 Damper Output" ; ph:dis "Bravo VAV 3-23 Damper Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f80-1ec2-3c93-f23c91a70cca . _:0b111ff8-3f80-1ec2-3c93-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime ; _:pointType "" . _:b-03eb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f80-1ec3-3c94-f23c91a70cca . _:0b111ff8-3f80-1ec3-3c94-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-03ec a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-23 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f80-1ec4-3c95-f23c91a70cca . _:0b111ff8-3f80-1ec4-3c95-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ed a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-23 Heating Valve Output" ; ph:dis "Bravo VAV 3-23 Heating Valve Output" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f80-1ec5-3c96-f23c91a70cca . _:0b111ff8-3f80-1ec5-3c96-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03ee a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-23 Supply Air Temperature" ; ph:dis "Bravo VAV 3-23 Supply Air Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ec6-3c97-f23c91a70cca . _:0b111ff8-3f80-1ec6-3c97-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03ef a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-23 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ec7-3c98-f23c91a70cca . _:0b111ff8-3f80-1ec7-3c98-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-03f0 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-23 Zone Temperature" ; ph:dis "Bravo VAV 3-23 Zone Temperature" ; phIoT:equipRef _:b-03e9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ec8-3c99-f23c91a70cca . _:0b111ff8-3f80-1ec8-3c99-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-03f1 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-24" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-24" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f80-1ec9-3c9a-f23c91a70cca . _:0b111ff8-3f80-1ec9-3c9a-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.4 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-03f2 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-24 Damper Output" ; ph:dis "Bravo VAV 3-24 Damper Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f80-1eca-3c9b-f23c91a70cca . _:0b111ff8-3f80-1eca-3c9b-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f3 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f80-1ecb-3c9c-f23c91a70cca . _:0b111ff8-3f80-1ecb-3c9c-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03f4 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-24 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f80-1ecc-3c9d-f23c91a70cca . _:0b111ff8-3f80-1ecc-3c9d-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-03f5 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-24 Heating Valve Output" ; ph:dis "Bravo VAV 3-24 Heating Valve Output" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f80-1ecd-3c9e-f23c91a70cca . _:0b111ff8-3f80-1ecd-3c9e-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-03f6 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-24 Supply Air Temperature" ; ph:dis "Bravo VAV 3-24 Supply Air Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Str" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ece-3c9f-f23c91a70cca . _:0b111ff8-3f80-1ece-3c9f-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03f7 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-24 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ecf-3ca0-f23c91a70cca . _:0b111ff8-3f80-1ecf-3ca0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-03f8 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-24 Zone Temperature" ; ph:dis "Bravo VAV 3-24 Zone Temperature" ; phIoT:equipRef _:b-03f1 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3f80-1ed0-3ca1-f23c91a70cca . _:0b111ff8-3f80-1ed0-3ca1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03f9 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-25" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-25" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3f80-1ed1-3ca2-f23c91a70cca . _:0b111ff8-3f80-1ed1-3ca2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 149 ; _:designHotWaterPower 16.6 ; _:designHotWaterFlow 2 ; _:designAirFlow 500 . _:b-03fa a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-25 Damper Output" ; ph:dis "Bravo VAV 3-25 Damper Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f8f-6100-3ca3-f23c91a70cca . _:0b111ff8-3f8f-6100-3ca3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-03fb a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f8f-6101-3ca4-f23c91a70cca . _:0b111ff8-3f8f-6101-3ca4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03fc a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-25 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3f8f-6102-3ca5-f23c91a70cca . _:0b111ff8-3f8f-6102-3ca5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-03fd a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-25 Heating Valve Output" ; ph:dis "Bravo VAV 3-25 Heating Valve Output" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3f8f-6103-3ca6-f23c91a70cca . _:0b111ff8-3f8f-6103-3ca6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-03fe a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-25 Supply Air Temperature" ; ph:dis "Bravo VAV 3-25 Supply Air Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fbd-27c0-3ca7-f23c91a70cca . _:0b111ff8-3fbd-27c0-3ca7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:10.497-04:00"^^xsd:dateTime . _:b-03ff a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-25 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fbd-27c1-3ca8-f23c91a70cca . _:0b111ff8-3fbd-27c1-3ca8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0400 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-25 Zone Temperature" ; ph:dis "Bravo VAV 3-25 Zone Temperature" ; phIoT:equipRef _:b-03f9 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fbd-27c2-3ca9-f23c91a70cca . _:0b111ff8-3fbd-27c2-3ca9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0401 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-26" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-26" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fbd-27c3-3caa-f23c91a70cca . _:0b111ff8-3fbd-27c3-3caa-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 12.9 ; _:designHotWaterFlow 1.5 ; _:designAirFlow 400 . _:b-0402 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-26 Damper Output" ; ph:dis "Bravo VAV 3-26 Damper Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fbd-27c4-3cab-f23c91a70cca . _:0b111ff8-3fbd-27c4-3cab-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0403 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fbd-27c5-3cac-f23c91a70cca . _:0b111ff8-3fbd-27c5-3cac-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0404 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-26 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fbd-27c6-3cad-f23c91a70cca . _:0b111ff8-3fbd-27c6-3cad-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0405 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-26 Heating Valve Output" ; ph:dis "Bravo VAV 3-26 Heating Valve Output" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fbd-27c7-3cae-f23c91a70cca . _:0b111ff8-3fbd-27c7-3cae-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0406 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-26 Supply Air Temperature" ; ph:dis "Bravo VAV 3-26 Supply Air Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a00-3caf-f23c91a70cca . _:0b111ff8-3fcc-6a00-3caf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0407 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-26 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a01-3cb0-f23c91a70cca . _:0b111ff8-3fcc-6a01-3cb0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0408 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-26 Zone Temperature" ; ph:dis "Bravo VAV 3-26 Zone Temperature" ; phIoT:equipRef _:b-0401 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a02-3cb1-f23c91a70cca . _:0b111ff8-3fcc-6a02-3cb1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0409 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-27" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-27" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fcc-6a03-3cb2-f23c91a70cca . _:0b111ff8-3fcc-6a03-3cb2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-040a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-27 Damper Output" ; ph:dis "Bravo VAV 3-27 Damper Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fcc-6a04-3cb3-f23c91a70cca . _:0b111ff8-3fcc-6a04-3cb3-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:07.473-04:00"^^xsd:dateTime . _:b-040b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fcc-6a05-3cb4-f23c91a70cca . _:0b111ff8-3fcc-6a05-3cb4-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:10.745-04:00"^^xsd:dateTime . _:b-040c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-27 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fcc-6a06-3cb5-f23c91a70cca . _:0b111ff8-3fcc-6a06-3cb5-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-040d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-27 Heating Valve Output" ; ph:dis "Bravo VAV 3-27 Heating Valve Output" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fcc-6a07-3cb6-f23c91a70cca . _:0b111ff8-3fcc-6a07-3cb6-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-040e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-27 Supply Air Temperature" ; ph:dis "Bravo VAV 3-27 Supply Air Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a08-3cb7-f23c91a70cca . _:0b111ff8-3fcc-6a08-3cb7-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime ; _:pointType "" . _:b-040f a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-27 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a09-3cb8-f23c91a70cca . _:0b111ff8-3fcc-6a09-3cb8-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0410 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-27 Zone Temperature" ; ph:dis "Bravo VAV 3-27 Zone Temperature" ; phIoT:equipRef _:b-0409 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a0a-3cb9-f23c91a70cca . _:0b111ff8-3fcc-6a0a-3cb9-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:10.62-04:00"^^xsd:dateTime . _:b-0411 a phIoT:thermostat, phIoT:vav ; ph:hasTag phIoT:equip, phIoT:fanPowered, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:thermostat, phIoT:vav, phIoT:zone ; rdfs:label "Bravo VAV 3-28" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-28" ; phIoT:hotWaterRef _:b-0012 ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fcc-6a0b-3cba-f23c91a70cca . _:0b111ff8-3fcc-6a0b-3cba-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 3 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 200 . _:b-0412 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cmd, phIoT:cur, phIoT:damper, phIoT:discharge, phIoT:his, phIoT:point ; rdfs:label "Bravo VAV 3-28 Damper Output" ; ph:dis "Bravo VAV 3-28 Damper Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fcc-6a0c-3cbb-f23c91a70cca . _:0b111ff8-3fcc-6a0c-3cbb-f23c91a70cca rdfs:label "" ; _:sourcePointName "DAMPER_CMD" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0413 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fcc-6a0d-3cbc-f23c91a70cca . _:0b111ff8-3fcc-6a0d-3cbc-f23c91a70cca rdfs:label "" ; _:sourcePointName "BOX_FLOW" ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-0414 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:effective, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; ph:dis "Bravo VAV 3-28 Discharge Air Flow Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fcc-6a0e-3cbd-f23c91a70cca . _:0b111ff8-3fcc-6a0e-3cbd-f23c91a70cca rdfs:label "" ; _:sourcePointName "FLOW_STPT" ; _:dataSyncRecovered "2020-07-10T01:00:10.995-04:00"^^xsd:dateTime . _:b-0415 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phIoT:cmd, phIoT:cur, phIoT:heat, phIoT:his, phIoT:hot, phIoT:point, phIoT:valve, phScience:water ; rdfs:label "Bravo VAV 3-28 Heating Valve Output" ; ph:dis "Bravo VAV 3-28 Heating Valve Output" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "%" ; _:custom _:0b111ff8-3fcc-6a0f-3cbe-f23c91a70cca . _:0b111ff8-3fcc-6a0f-3cbe-f23c91a70cca rdfs:label "" ; _:sourcePointName "Htg" ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0416 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp ; rdfs:label "Bravo VAV 3-28 Supply Air Temperature" ; ph:dis "Bravo VAV 3-28 Supply Air Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a10-3cbf-f23c91a70cca . _:0b111ff8-3fcc-6a10-3cbf-f23c91a70cca rdfs:label "" ; _:sourcePointName "DisAirTemp" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0417 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sp, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Air Temp Setpoint" ; ph:dis "Bravo VAV 3-28 Zone Air Temp Setpoint" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fcc-6a11-3cc0-f23c91a70cca . _:0b111ff8-3fcc-6a11-3cc0-f23c91a70cca rdfs:label "" ; _:sourcePointName "STAT_SETPOINT" ; _:dataSyncRecovered "2020-07-10T01:00:09.627-04:00"^^xsd:dateTime . _:b-0418 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phIoT:zone ; rdfs:label "Bravo VAV 3-28 Zone Temperature" ; ph:dis "Bravo VAV 3-28 Zone Temperature" ; phIoT:equipRef _:b-0411 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "\u00b0F" ; _:custom _:0b111ff8-3fdb-ac40-3cc1-f23c91a70cca . _:0b111ff8-3fdb-ac40-3cc1-f23c91a70cca rdfs:label "" ; _:sourcePointName "SPACE_TEMP" ; _:dataSyncRecovered "2020-07-10T01:00:13.145-04:00"^^xsd:dateTime . _:b-0419 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-3" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-3" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fdb-ac41-3cc2-f23c91a70cca . _:0b111ff8-3fdb-ac41-3cc2-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 4.2 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 375 . _:b-041a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-3 Supply Air Flow" ; ph:dis "Bravo VAV 3-3 Supply Air Flow" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac42-3cc3-f23c91a70cca . _:0b111ff8-3fdb-ac42-3cc3-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-041b a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-3 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-3 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0419 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac43-3cc4-f23c91a70cca . _:0b111ff8-3fdb-ac43-3cc4-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-041c a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-4" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-4" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fdb-ac44-3cc5-f23c91a70cca . _:0b111ff8-3fdb-ac44-3cc5-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 155 ; _:designHotWaterPower 1.7 ; _:designHotWaterFlow 0.5 ; _:designAirFlow 150 . _:b-041d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-4 Supply Air Flow" ; ph:dis "Bravo VAV 3-4 Supply Air Flow" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac45-3cc6-f23c91a70cca . _:0b111ff8-3fdb-ac45-3cc6-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.87-04:00"^^xsd:dateTime . _:b-041e a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-4 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-4 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041c ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac46-3cc7-f23c91a70cca . _:0b111ff8-3fdb-ac46-3cc7-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.721-04:00"^^xsd:dateTime . _:b-041f a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-5" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-5" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fdb-ac47-3cc8-f23c91a70cca . _:0b111ff8-3fdb-ac47-3cc8-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 3.3 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0420 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-5 Supply Air Flow" ; ph:dis "Bravo VAV 3-5 Supply Air Flow" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac48-3cc9-f23c91a70cca . _:0b111ff8-3fdb-ac48-3cc9-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:11.125-04:00"^^xsd:dateTime . _:b-0421 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-5 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-5 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-041f ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac49-3cca-f23c91a70cca . _:0b111ff8-3fdb-ac49-3cca-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.752-04:00"^^xsd:dateTime . _:b-0422 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-6" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-6" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fdb-ac4a-3ccb-f23c91a70cca . _:0b111ff8-3fdb-ac4a-3ccb-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 152 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 600 . _:b-0423 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-6 Supply Air Flow" ; ph:dis "Bravo VAV 3-6 Supply Air Flow" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac4b-3ccc-f23c91a70cca . _:0b111ff8-3fdb-ac4b-3ccc-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.003-04:00"^^xsd:dateTime . _:b-0424 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-6 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-6 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0422 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac4c-3ccd-f23c91a70cca . _:0b111ff8-3fdb-ac4c-3ccd-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-0425 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-7" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-7" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fdb-ac4d-3cce-f23c91a70cca . _:0b111ff8-3fdb-ac4d-3cce-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 150 ; _:designHotWaterPower 7.6 ; _:designHotWaterFlow 1.25 ; _:designAirFlow 700 . _:b-0426 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-7 Supply Air Flow" ; ph:dis "Bravo VAV 3-7 Supply Air Flow" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fdb-ac4e-3ccf-f23c91a70cca . _:0b111ff8-3fdb-ac4e-3ccf-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-0427 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-7 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-7 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0425 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fea-ee80-3cd0-f23c91a70cca . _:0b111ff8-3fea-ee80-3cd0-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.249-04:00"^^xsd:dateTime . _:b-0428 a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-8" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-8" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fea-ee81-3cd1-f23c91a70cca . _:0b111ff8-3fea-ee81-3cd1-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 153 ; _:designHotWaterPower 6.5 ; _:designHotWaterFlow 0.75 ; _:designAirFlow 300 . _:b-0429 a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-8 Supply Air Flow" ; ph:dis "Bravo VAV 3-8 Supply Air Flow" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fea-ee82-3cd2-f23c91a70cca . _:0b111ff8-3fea-ee82-3cd2-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:07.598-04:00"^^xsd:dateTime . _:b-042a a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-8 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-8 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-0428 ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fea-ee83-3cd3-f23c91a70cca . _:0b111ff8-3fea-ee83-3cd3-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.374-04:00"^^xsd:dateTime . _:b-042b a phIoT:vav ; ph:hasTag phIoT:equip, phIoT:hotWaterHeating, phIoT:hvac, phIoT:singleDuct, phIoT:vav ; rdfs:label "Bravo VAV 3-9" ; phIoT:airRef _:b-00f2 ; ph:dis "Bravo VAV 3-9" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; _:custom _:0b111ff8-3fea-ee84-3cd4-f23c91a70cca . _:0b111ff8-3fea-ee84-3cd4-f23c91a70cca rdfs:label "" ; _:designSource "Drawings" ; _:designHotWaterEnteringTemp 180 ; _:designHotWaterLeavingTemp 151 ; _:designHotWaterPower 23 ; _:designHotWaterFlow 4 ; _:designAirFlow 2000 . _:b-042c a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Bravo VAV 3-9 Supply Air Flow" ; ph:dis "Bravo VAV 3-9 Supply Air Flow" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fea-ee85-3cd5-f23c91a70cca . _:0b111ff8-3fea-ee85-3cd5-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:09.879-04:00"^^xsd:dateTime . _:b-042d a phIoT:cur-point, phIoT:his-point ; ph:hasTag phScience:air, phIoT:cur, phIoT:discharge, phScience:flow, phIoT:his, phIoT:point, phIoT:sp ; rdfs:label "Bravo VAV 3-9 Supply Air Flow Setpoint" ; ph:dis "Bravo VAV 3-9 Supply Air Flow Setpoint" ; phIoT:equipRef _:b-042b ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; phIoT:spaceRef _:b-042e ; ph:tz "Chicago" ; ph:unit "cfm" ; _:custom _:0b111ff8-3fea-ee86-3cd6-f23c91a70cca . _:0b111ff8-3fea-ee86-3cd6-f23c91a70cca rdfs:label "" ; _:dateCreated "2020-04-03"^^xsd:date ; _:dataSyncRecovered "2020-07-10T01:00:10.126-04:00"^^xsd:dateTime . _:b-042e a phIoT:space ; ph:hasTag phIoT:space ; rdfs:label "Bravo VAVs" ; ph:dis "Bravo VAVs" ; phIoT:siteRef _:b-0000 ; _:custom _:0b111ff8-3fea-ee87-3cd7-f23c91a70cca . _:0b111ff8-3fea-ee87-3cd7-f23c91a70cca rdfs:label "" . _:b-042f a phIoT:weatherStation ; ph:hasTag phIoT:weatherStation ; rdfs:label "Fort Wayne, IN" ; ph:dis "Fort Wayne, IN" ; ph:geoCity "Fort Wayne" ; ph:geoCoord "C(41.131,-85.129)"^^ph:coord ; ph:geoCountry "US" ; ph:geoState "IN" ; ph:tz "Indianapolis" . _:b-0430 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor, phScience:weather, phScience:weatherCond ; rdfs:label "Fort Wayne, IN Condition" ; ph:dis "Fort Wayne, IN Condition" ; ph:enum "unknown,clear,partlyCloudy,cloudy,showers,rain,thunderstorms,ice,flurries,snow" ; ph:kind "Str" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0431 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phScience:humidity, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Humidity" ; ph:dis "Fort Wayne, IN Humidity" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "%RH" ; phIoT:weatherStationRef _:b-042f . _:b-0432 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:daytime, phIoT:his, phIoT:point, phIoT:sensor, phScience:weather ; rdfs:label "Fort Wayne, IN Sunrise" ; ph:dis "Fort Wayne, IN Sunrise" ; ph:kind "Bool" ; ph:tz "Indianapolis" ; phIoT:weatherStationRef _:b-042f . _:b-0433 a phIoT:his-point, phIoT:weather-point ; ph:hasTag phScience:air, phIoT:his, phIoT:point, phIoT:sensor, phScience:temp, phScience:weather ; rdfs:label "Fort Wayne, IN Temp" ; ph:dis "Fort Wayne, IN Temp" ; ph:kind "Number" ; ph:tz "Indianapolis" ; ph:unit "\u00b0F" ; phIoT:weatherStationRef _:b-042f . _:b-0434 a phIoT:his-point ; ph:hasTag phIoT:his, phIoT:point, phIoT:sensor ; rdfs:label "Points Not Syncing" ; ph:dis "Points Not Syncing" ; ph:kind "Number" ; phIoT:siteRef _:b-0000 ; ph:tz "Chicago" ; _:custom _:0b111ff8-3fea-ee88-3cd8-f23c91a70cca . _:0b111ff8-3fea-ee88-3cd8-f23c91a70cca rdfs:label "" ; _:dataSyncRecovered "2020-07-14T01:00:05.167-04:00"^^xsd:dateTime .